Viessmann VITOTRONIC 100 GC1 Installation And Service Instructions Manual page 24

Digital boiler control unit
Table of Contents

Advertisement

Heating system types
Circuit Diagram 9
IMPORTANT
This circuit diagram represents a
recommendation only. It is the
responsibility of the customer and/or
heating contractor to check that this
recommendation is complete and fully
functional. Three-phase equipment
must be connected via additional
power contactors.
Available system accessories
Flue gas temperature sensor
Coding of
Change required
system type
00: 1
02: 1
Set coding "02: 2" for operation with
modulating burner
0C: 4
Set coding "0C: 0"
0d: 2
Set coding "0d: 0"
24
(continued)
The Vitocrossal 300 is operated with
constant boiler water temperature by
means of the boiler control unit.
Two-stage or modulating burners
can be controlled.
The boiler water temperature which is
established in the heating mode is
higher than the maximum heating
system supply temperature by an
adjustable difference.
–––
Automatic change
With DHW tank:
Coding is automatically changed to "00: 2"
–––
–––
–––