Viessmann VITOTRONIC 100 GC1 Installation And Service Instructions Manual page 118

Digital boiler control unit
Table of Contents

Advertisement

Additional information
Coding 2
(continued)
Overview of all codings (continued)
Coding as per
Function
factory setting
Address: Value
03: 0
Boiler/
burner
*1
04:
Boiler/
burner
05: 70
05: 70
Burner
Burner
(mod.)
(mod.)
*1
The factory setting is determined by the boiler coding card.
118
Gas-fired operation
Switching differential
Burner curve
Burner curve
New coding
Possible change
Address: Value
03: 1
Oil-fired operation
(coding cannot be reset)
04: 0
Switching differential 4°C / 7°F
ON
OFF
Set-
point
Low
heat demand
Switching differential heat demand-
controlled
ERB50 function
04: 1
Values from 6 to 12°C / 11 to 22°F are
set, depending on the heat demand.
ON
OFF
Set-
point
Low
heat demand
ERB80 function
Values from 6 to 20°C / 11 to 36°F are
04: 2
set, depending on the heat demand.
ON
OFF
Set-
point
Low
heat demand
The heat demand-controlled switching
differential takes into account the boiler
load. The switching differential, i.e. the
burner operating time, is varied in
relation to the actual heat demand.
05: 0
Burner curve linear
05: 1
Burner curve not linear
to
05: 99
Partial output in kW (at g of the
Operating
time of the actuating drive)
Max. output in kW
= Partial output in %
Time
Medium
High
heat demand
heat demand
Time
High
Medium
heat demand
heat demand
Time
Medium
High
heat demand
heat demand
x100 %