Viessmann VITOTRONIC 100 GC1 Installation And Service Instructions Manual page 91

Digital boiler control unit
Table of Contents

Advertisement

Steps
(continued)
7. Match the coding addresses (continued)
10. Set the established values in coding
level 1.
Address Setting of
05
the partial output (see point 8) as a percentage proportion of the
max. output; e.g.
partial output: 170 kW
max. output: 210 kW
170 kW
x100 % = 81 %
210 kW
08
units and tens digits of the maximum output established in point
4: e.g. max. output: 210 kW – here set: 10
09
hundreds digit of the maximum output established in point 4: e.g.
max. output: 210 kW – here set: 2
0A
the basic output (see point 6) as a percentage proportion of the
max. output; e.g.
basic output: 70 kW
max. output: 210 kW
70 kW
x100 % = 33 %
210 kW
15
the operating time in seconds established in point 5
Please note:
You will find details of other possible settings in the sections entitled
"Coding 1" and "Coding 2" (see page 115 and 117).
Start-up
See page 115 for coding 1.