Viessmann VITOTRONIC 100 GC1 Installation And Service Instructions Manual page 98

Digital boiler control unit
Table of Contents

Advertisement

Scanning service information
Scanning and Resetting the Service Display
98
Please note:
If a service is carried out before the service display appears, set the coding
address "24: 1" and then coding address "24: 0".
When the limit values selected via
coding addresses "1F", "21" and "23"
(see page 120) are reached, one of the
following displays flashes on the
programming unit:
Display
Meaning
a 245
°C Max. flue gas
temperature reached
35510
Number of burner hours
h
run reached
12
Time interval
u
(e.g. 12 months)
reached
1. Scan the service messages with the
or
button.
2. Press
.
After carrying out maintenance
1. Reset coding "24: 1"
(see page 120) to "24: 0".
2. If necessary:
Press
.
Reset burner hours run and
number of burner starts with
the
button.
Press
.
3. If necessary:
Press
and
simultaneously for approx.
4 seconds.
Reset maximum flue gas
temperature (8) to the actual
value by pressing
.
Press
.
The service display is turned off.
Please note:
An acknowledged service message
can be displayed again by pressing
(for approx. 3 seconds).
Please note:
If coding address "24" is not reset,
the service display will re-appear on
Monday morning.
See "Temperatures, boiler coding
cards and scans" on page 93.
See "Scanning operating status
information" on page 97.