Power Supply Unit Board; Electronics Board; Optolink/Override Switch Board - Viessmann VITOTRONIC 100 GC1 Installation And Service Instructions Manual

Digital boiler control unit
Table of Contents

Advertisement

Additional information
System Components
Power supply unit board, 120 VAC Part No. 7823 991
Electronics board, Part No. 7828 193
Optolink/override switch board, Part No. 7820 165
110
(continued)
The circuit board contains:
Operating status indicator
Fault indicator
Optolink laptop interface
Override switch
The power supply unit board contains
the low-voltage supply for the entire
electronics.
The board contains the microprocessor
with the software.
When replacing the board:
1. Make a note of codings and settings
on the control unit.
2. Replace the board.
3. Set coding "8A:176" and set
cod-ing address "92" (not listed in
the overview) to "92:160".
Override switch for flue gas
measurements with the boiler operated
with constant boiler water temperature
for a short time.
The following functions are triggered in
the "h" setting:
The burner is switched on
(this can be delayed if the system
incorporates a fuel preheater or flue
gas damper)
All pumps are switched on
The boiler water temperature is
controlled by the adjustable high limit
"R".