Viessmann VITOTRONIC 100 GC1 Installation And Service Instructions Manual page 119

Digital boiler control unit
Table of Contents

Advertisement

Coding 2
((continued)
Overview of all codings (continued)
Coding as per
Function
factory setting
Address: Value
06: 87
Max. limit of boiler water
Boiler/
temperature set to
burner
87°C / 189°F
07: 1
Boiler sequence number in multi-
Boiler
boiler system (in conjunction with
coding address "01")
*1
08:
Max. output of burner in kW
Burner
(mod.)
*1
09:
Max. output of burner in kW
Burner
(mod.)
*1
0A:
Basic output of burner in %
Burner
(mod.)
0C: 5
0C: 5
Boiler isolation valve controlled on
Boiler isolation valve controlled on
Boiler
Boiler
a modulating basis independently
a modulating basis independently
of the set-point boiler water
of the set-point boiler water
temperature
temperature
0d: 2
0d: 2
With Therm-Control, effective for
With Therm-Control, effective for
Boiler
Boiler
boiler isolation valve (function not
boiler isolation valve (function not
active if "0C: 1" is coded)
*1
13:
13:
Switch-off differential in °C / °F
Switch-off differential in °C / °F
Boiler/
Boiler/
The burner is switched off when
The burner is switched off when
burner
burner
the boiler water temperature rises
above the set-point value
*1
14:
Minimum operating time in
Burner
minutes
*2
15: 10
Operating time of actuating drive
Boiler/
10 seconds
burner
(mod.)
*1
16:
Mod. burner offset in °C / °F
Burner
Temporary reduction of the boiler
(mod.)
set-point value after burner start
*1
1A:
Optimized start-up in minutes
Burner
(mod.)
*1
The factory setting is determined by the boiler coding card.
*2
These settings are matched to the Vitocrossal.
New coding
Possible change
Address:
Value
06: 20
Maximum boiler water temperature limit
to
variable between 20 and 127
06:127
07: 2
Boiler sequence number in multi-boiler
to
system
07: 4
(in conjunction with coding address "01")
08: 0
Maximum output variable from
to
0 to 99 kW;
08: 99
1 increment = 1 kW
09: 0
Maximum output variable from
0 to 19 900 kW;
to
09:199
1 increment = 100 kW
0A: 0
Basic output in kW
to
Max. output in kW
0A:100
Basic output in %
0C: 0
Without function
0C: 1
Continuous return temperature control
0C: 2
Boiler isolation valve time-controlled
0C: 3
Boiler isolation valve temperature-controlled
0C: 4
Boiler isolation valve controlled on a
modulating basis as a function of the set
point boiler water temperature
0d: 0
Without Therm-Control
With Therm-Control, effective for mixing
0d: 1
valve of heating circuits connected
downstream
13: 0
Without switch-off differential
13: 2
Switch-off differential variable from
to
2 to 20°C / 4 to 36°F
13: 20
14: 0
Minimum operating time variable
to
from 0 to 15 minutes
14: 15
15: 5
Operating time variable
to
from 5 to 199 seconds
15:199
16: 0
Offset during optimized start-up
to
adjustable from 0 to 15°C / 0 to 27°F
16: 15
1A: 0
Duration of optimized start-up
to
adjustable from 0 to 60 minutes
1A: 60
Additional information
x100% =
119