Viessmann VITOTRONIC 100 GC1 Installation And Service Instructions Manual page 87

Digital boiler control unit
Table of Contents

Advertisement

Steps
(continued)
3. Integrate the control unit in the LON BUS system
1 2 3 4 5 6 7
Example of single-boiler system with Vitotronic 050 heating circuit controls and Vitocom connected downstream
Vitotronic 100
LON
Participant No. 1
Coding "77: 1"
Control unit is error
manager
Coding "79: 1"
–––
–––
The LON communication module
(accessory) must be inserted
(see page 111).
Set the LON participant number
Set the LON participant number via
coding address "77" in coding 1
(factory setting: "77: 1").
Update the LON participant list
This is only possible when all participants are connected and the control unit is
coded as the error manager (coding "79: 1").
1. Press w and
approx. 2 seconds.
2. Press D.
Vitotronic 050
LON
Participant No. 10
Coding "77: 10"
Control unit is not error
manager
Coding "79: 0"
Transmit time via LON
Set coding "7b: 1"
Transmit outdoor
temperature via LON
Set coding "97: 2"
See page 115 for coding 1.
Please note:
The same number must not be
assigned twice within a LON BUS
system.
simultaneously for
The participant check is initiated
(see also page 88).
The participant list is updated after
approx. 2 minutes.
The participant check is terminated.
Vitotronic 050
LON
Participant No. 11
Set coding "77: 11"
Control unit is not error
manager
Coding "79: 0"
Time is received via LON
Set coding "81: 3"
Outdoor temperature is
received via LON
Set coding "97: 1"
Start-up
Single-boiler system only
Vitocom
Participant No. 100
Unit is error manager
Time is received via LON
–––
87