Outdoor Fan Pcb Abnormality - Daikin REYQ-XA Service Manual

Table of Contents

Advertisement

Troubleshooting by Error Code

3.45 Outdoor Fan PCB Abnormality

H7
Error Code
Applicable
REYQ-XAYCU
Models
Method of Error
Detect with current sensor value.
Detection
Error Decision
When the current sensor shows abnormality.
Conditions
Supposed
Defective fan PCB (A5P, A6P)
Causes
Troubleshooting
∗1: Fan PCB and connectors
Note:
313
Be sure to turn off the power switch before connecting or disconnecting
Caution
connectors, or parts may be damaged.
Check for fan PCB applicable to the error code H7 while in
monitor mode.
H7-21/23/25: Fan PCB (A6P) Master / Slave 1 / Slave 2
H7-22/24/26: Fan PCB (A5P) Master / Slave 1 / Slave 2
Turn OFF the power supply
and wait for 10 minutes.
Is the
connector of
relevant fan motor
normally connected?
(∗1)
Resistance
between U, V, W
phases of the fan motor
power supply cable has lost
balance or short circuit is
caused between U,
V, W phases.
Fan motor
Fan PCB
M1F
A6P
M2F
A5P
NO
YES
NO
YES
Connector
X1A
X1A
SiUS371901E
Properly connect the connector.
Replace the relevant fan motor.
(M1F, M2F)
Replace the fan PCB. (∗1)