Specifications; Reyq-Xatju - Daikin REYQ-XA Service Manual

Table of Contents

Advertisement

Specifications

5. Specifications
5.1

REYQ-XATJU

Model name
Power supply
Nominal
1 Cooling capacity
Rated
Nominal
2 Heating capacity
Rated
Casing color
Dimensions: (H × W × D)
Heat exchanger
Type
Volume
Number of revolutions
Compressor
Motor output ×
Number of units
Starting method
Type
Motor output
Fan
Airflow rate
Drive
Liquid pipe
Connecting
Suction gas pipe
pipes
High/Low pressure gas pipe
Weight
Sound pressure level (Reference data)
Sound power level (Reference data)
Safety devices
Defrost method
Capacity control
Refrigerant name
Refrigerant
Charge
Control
Standard accessories
Drawing No.
Specification
Notes:
1 Indoor temp.: 80°FDB (26.7°CDB), 67°FWB (19.4°CWB)/Outdoor temp.: 95°FDB (35.0°CDB)/Rated capacity is certified under AHRI standard 1230.
2 Indoor temp.: 70°FDB (21.1°CDB)/Outdoor temp.: 47°FDB (8.3°CDB), 43°FWB (6.1°CWB)/Rated capacity is certified under AHRI standard 1230.
11
Btu/h
(kW)
Btu/h
(kW)
in (mm)
3
m
/h
r/min
kW
kW
cfm
3
(m
/min)
in (mm)
in (mm)
in (mm)
lbs (kg)
dB (A)
dB
High pressure switch, Fan driver overload protector, Overcurrent fuse,
%
lbs (kg)
REYQ72XATJU
3 phase, 208/230 V, 60 Hz
72,000 (21.1)
69,000 (20.2)
81,000 (23.7)
77,000 (22.6)
Ivory white (5Y7.5/1)
66-11/16 × 48-7/8 × 30-3/16 (1,694 × 1,242 × 767)
Cross fin coil
Hermetically sealed scroll type
12.7
3,738
3.9 × 1
Soft start
Propeller fan
0.8 × 2
7,283 (206)
Direct drive
φ3/8 (9.5) C1220T (Brazing connection)
φ3/4 (19.1) C1220T (Brazing connection)
φ5/8 (15.9) C1220T (Brazing connection)
727 (330)
65
79
Inverter overload protector, Leak detecting device
Deicer
15-100
R-410A
25.8 (11.7)
Electronic expansion valve
Installation manual, Operation manual, Connection pipes, Clamps
3D120068A
SiUS371901E
General Information