Outdoor Fan Motor Abnormality - Daikin REYQ-XA Service Manual

Table of Contents

Advertisement

SiUS371901E

3.37 Outdoor Fan Motor Abnormality

3.37.1 Outdoor Fan Motor Abnormality (REYQ-XATJU, REYQ-XAYDU)
E7
Error Code
Applicable
REYQ-XATJU, REYQ-XAYDU
Models
Method of Error
Detection
Error Decision
Conditions
Supposed
Causes
Troubleshooting
Service Diagnosis
Detects according to the value of current flowing through the inverter PCB (or fan PCB in case
of M2F).
Detects error of the fan motor system according to the fan revolutions detected by the Hall IC
during the fan motor runs.
Overcurrent is detected from the inverter PCB or the fan PCB (Detecting overcurrent 4 times will
shut down the system).
The fan revolutions fall below a given level for a period of 6 seconds while in fan motor rotation
mode (Detecting shortage of revolutions will shut down the system).
Fan motor failure
Neglect to connect or defective connection of harness/connector between the fan motor and the
PCB
Fan does not rotate due to foreign matter caught in it.
Clearing condition: fan motor performs normal operation for a period of 5 minutes
Be sure to turn off the power switch before connecting or disconnecting
Caution
connectors, or parts may be damaged.
Check in Monitor Mode
Outdoor units are equipped with 2 fan motors.
Check for M1F or M2F applicable to the error code E7 while in
monitor mode of the outdoor unit.
Turn OFF the power supply, and then wait for a period of 10 minutes.
There are
foreign matter around the
applicable fan.
NO
Check for Connection of Connector
Check for the connections of all fan motor connectors.
Some connectors are
disconnected.
NO
Check for Colors of Connectors
Check for any wire connection errors in 2 units of fan motors.
M1F: Power supply cables and signal cables are all white.
M2F: Power supply cables and signal cables are red on the
PCB side and white on the motor side.
There is a relay
connection error.
NO
Go to the next page.
A
YES
YES
YES
Troubleshooting by Error Code
Remove the foreign matter.
Insert the connector.
Correct the connection of the
connector.
300

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Reyq72-456xatjuReyq72-456xa yduReyq72-432xa ycu

Table of Contents