1. Field Settings for Indoor Unit

1.1

Field Settings with Remote Controller

Individual function of indoor unit can be changed from the remote controller. At the time of installation or after
service inspection / repair, make the field setting in accordance with the following description.
Wrong setting may cause error.
(When optional accessory is mounted on the indoor unit, setting for the indoor unit may be required to change.
Refer to information in the option handbook.)
1.1.1 Wired Remote Controller
BRC1E73
In the case of individual
setting per indoor unit
(3)
(4)
(5)
Field Settings and Test Operation
<Basic screen>
(1)
Press and hold Cancel
button for 4 seconds or
more during backlight lit.
<Service Settings menu screen>
(2)
Press Menu/OK button.
<Service Settings screen>
In the case of group total
(3)
(5)
SECOND CODE NO.
FIRST CODE (SW) NO.
Press Menu/OK button.
setting
Field Settings for Indoor Unit
1.
Press and hold Cancel button for
4 seconds or more.
Service settings menu is
displayed.
2.
Select Field Settings in the
Service Settings menu, and
press Menu/OK button.
Field settings screen is
displayed.
3.
Highlight the mode, and select
desired Mode No. by using
(Up/Down) button.
4.
In the case of setting per indoor
unit during group control (When
Mode No. such as 20, 21, 22,
23, 25 are selected), highlight the
unit No. and select Indoor unit
No. to be set by using
(Up/Down) button.
(In the case of group total setting,
this operation is not needed.)
In the case of individual setting
per indoor unit, current settings
are displayed. And, SECOND
CODE NO. " - " means no
function.
5.
Highlight SECOND CODE NO. of
the FIRST CODE NO. to be
changed, and select desired
SECOND CODE NO. by using
(Up/Down) button. Multiple
identical mode number settings
are available.
In case of setting for all indoor
units in the remote control
group, available SECOND
CODE NO. is displayed as " ∗ "
which means it can be
changed.
When SECOND CODE NO. is
displayed as " - ", there is no
function.