Fan Motor Connector Check (Signal Cable) - Daikin REYQ-XA Service Manual

Table of Contents

Advertisement

Check

4.12 Fan Motor Connector Check (Signal Cable)

CHECK 17
Resistance measuring points and judgment criteria
Indoor unit
FXFQ-T, FXZQ-TA, FXUQ-P, FXSQ05-48TA, FXMQ07-12PB
Orange
FXEQ-P
Orange (3)
FXAQ-P
Orange (5)
FXSQ54TA, FXMQ15-54PB
Orange (3)
Yellow (1)
391
White
(1)
FG
(2)
Vsp
Brown
(3)
Vcc
Blue
(4)
GND
(5)
(6)
Red
(7)
Vdc
— (1)
White (2)
FG
Vsp
Brown (4)
Vcc
Blue (5)
GND
— (6)
— (7)
Red (8)
Vdc
White (6)
FG
Vsp
Brown (4)
Vcc
Blue (3)
GND
— (2)
Red (1)
Vdc
Gray (5)
GND
Pink (4)
Vcc
Hw
Blue (2)
H
V
H
U
Judgment criteria
Criteria
Measuring point
1 Ω
1 - 4
1 Ω
2 - 4
1 Ω
3 - 4
1 Ω
7 - 4
Judgment criteria
Measuring point
Criteria
1 Ω
2 - 5
1 Ω
3 - 5
1 Ω
4 - 5
1 Ω
8 - 5
Judgment criteria
Measuring point
Criteria
1 Ω
6 - 3
1 Ω
5 - 3
1 Ω
4 - 3
1 Ω
1 - 3
Judgment criteria
Criteria
Measuring point
1 Ω
5 - 4
1 Ω
5 - 3
1 Ω
5 - 2
1 Ω
5 - 1
SiUS371901E
Service Diagnosis

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Reyq72-456xatjuReyq72-456xa yduReyq72-432xa ycu