Blower Motor Not Running - Daikin REYQ-XA Service Manual

Table of Contents

Advertisement

Troubleshooting by Error Code
3.9

Blower Motor Not Running

A6
Error Code
Applicable
FXTQ-TA
Models
Outline
Error is issued if the indoor unit determines that the indoor fan motor cannot rotate.
Error Decision
Conditions
Error Reset
Reset by remote controller
Conditions
Supposed
Causes
Corrective
Actions
263
Determining successive abnormalities
Checks the rotation speed at 5-second intervals using the feedback of the fan motor.
If that figure falls below 50 rpm 5 times successively, it is deemed abnormal operation.
If, during operation, the rotation command is stopped, the 5-second interval check is halted and
the counted number will be cleared.
Determining long-term abnormalities
Checks the rotation speed at 5-second intervals using the feedback of the fan motor.
Performs rotation sampling 720 times (takes approximately one hour), and if the rotation speed
falls below 50 rpm over 100 times, it is deemed abnormal operation.
When the sampling reaches 720 times, the counted number will be cleared and the 720 times
sampling restarts.
If, during this, the rotation command is stopped, the 5-second interval check is halted, but the
counted number will be kept.
When the rotation command is restarted, the checks will resume.
Fan or motor obstruction
Power interruption (low voltage)
Incorrect or loose wiring
Check for obstruction on the fan or motor.
Verify the input voltage at the motor.
Check wiring or tighten wiring connections if needed.
Replace the indoor unit control PCB or motor.
CHECK 19
Refer to page 396.
SiUS371901E
Service Diagnosis