System Abnormality, Refrigerant System Address Undefined - Daikin REYQ-XA Service Manual

Table of Contents

Advertisement

SiUS371901E
3.76 System Abnormality, Refrigerant System Address
Undefined
UH
Error Code
Applicable
All indoor unit models
All outdoor unit models
Models
Method of Error
Detect an indoor unit with no auto address setting.
Detection
Error Decision
The error decision is made as soon as the abnormality aforementioned is detected.
Conditions
Supposed
Causes
Service Diagnosis
Improper connection of transmission wiring between indoor-outdoor units and outdoor-outdoor
units
Defective indoor unit control PCB
Defective outdoor unit main PCB (A1P)
Troubleshooting by Error Code
370