Details Of Field Settings For Indoor Unit - Daikin REYQ-XA Service Manual

Table of Contents

Advertisement

SiUS371901E
1.3

Details of Field Settings for Indoor Unit

Filter Cleaning Sign Interval, Filter Type
Setting
Model
Setting
Model
Thermistor Selection
Select a thermistor to control room temperature.
When the unit is not equipped with an infrared presence/floor sensor:
Mode No.
10 (20)
The factory setting for the Second Code No. is 01 and room temperature is controlled by the suction air
thermistor and remote controller thermistor.
When the Second Code No. is set to 02, room temperature is controlled by the suction air thermistor.
When the Second Code No. is set to 03, room temperature is controlled by the remote controller thermistor.
Field Settings and Test Operation
10 (20)-1
Filter contamination heavy/light
10 (20)-0
FXFQ-T
FXZQ-TA
FXUQ-P
FXEQ-P
FXDQ-M
FXSQ-TA
FXMQ-PB
FXMQ-M
FXHQ-M
FXLQ-M
FXNQ-M
FXAQ-P
10 (20)-1
Filter contamination heavy/light
10 (20)-0
FXTQ-TA
CXTQ-TA
First Code No.
2
01: Long life filter
Light
01
2,500 hrs.
200 hrs.
01: Short interval
Light
01
2,500 hrs.
Second Code No.
Remote controller thermistor and suction air
01
thermistor
02
Suction air thermistor only
03
Remote controller thermistor only
Field Settings for Indoor Unit
02: Ultra long life filter
Heavy
Light
02
01
1,250 hrs.
10,000 hrs.
100 hrs.
200 hrs.
02: Long interval
Heavy
Light
02
01
1,250 hrs.
10,000 hrs.
Contents
Heavy
02
5,000 hrs.
100 hrs.
Heavy
02
5,000 hrs.
170