3.49 Inverter PCB Abnormality

L1
Error Code
Applicable
All outdoor unit models
Models
Method of Error
Detection
Error Decision
Conditions
Supposed
Causes
Service Diagnosis
Detect according to current value detected during the output of waveform before compressor
startup
Detect according to current value detected with the current sensor during synchronous
operation for startup
When overcurrent flows during the output of waveform
When the current sensor error during synchronous operation
When IPM error occurs
Inverter PCB
IPM failure
Current sensor failure
Drive circuit failure