Field Wiring; Maintenance; Terminal Descriptions - Daikin IOM 1177-1 Installation Operation & Maintenance

Room temperature sensor – adjustable cool/warm with occupancy switch
Table of Contents

Advertisement

Installation

Field Wiring

Wiring between the sensor and the water source heat pump
unit for typical heating and cooling operation is shown in
Figure
3.
Figure 3: Field wiring
SmartSource™ Board
Terminal Block Label
Description
Terminal Label
Typical Wiring
Terminal Label
Description
Adjustable Cool/Warm Room Temperature Sensor with Occupancy Switch (Part No. 910121753)

Maintenance

Wipe the thermostat case as needed with a damp, water only
cotton cloth. Do not use any type of cleaner as it may damage
the buttons or labeling. Do not paint.

Terminal Descriptions

1 – Unit Status Indicator Input from the MicoTech III
SmartSource Unit Controller. (5VDC)
2 - Output Signal, Fan and Unit Mode (0 to 5VDC)
3 - Output Signal, Setpoint Adjustment
4 - Output Signal, Room Temp Thermistor Sensor. (10K ATP
Z curve, 10K-2)
5 - Ground or Neutral. Common Reference for All Signal
Terminals
E – Emergency Shutdown. (Terminal grounded when in
System "Off" mode)
U - Unoccupied Contact. (Terminal grounded when in
Unoccupied)
TB1-1
TB1-2
TB1-3
1
2
3
1
2
3
MicroTech ® III Board
Base Board
TB1-4
TB1-5
4
5
4
5
TB3-1
TB3-2
E
U
E
U
IOM 1177-1 / LIAF184 / Page 5 of 8