Preparing Refrigerant Piping; Refrigerant Piping Requirements; Refrigerant Piping Insulation; Preparing Water Piping - Daikin Altherma EVLQ05+08CA Installer's Reference Manual

Hybrid heat pump
Hide thumbs Also See for Altherma EVLQ05+08CA:
Table of Contents

Advertisement

6
|
Preparation

6.3 Preparing refrigerant piping

6.3.1 Refrigerant piping requirements

6.3.2 Refrigerant piping insulation

6.4 Preparing water piping

Installer reference guide
44
INFORMATION
Also read the precautions and requirements in the
4
precautions" [
Piping material: Phosphoric acid deoxidised seamless copper.
Piping diameter:
Liquid piping
Gas piping
Piping temper grade and thickness:
Outer diameter (Ø)
6.4 mm (1/4")
15.9 mm (5/8")
(a)
Depending on the applicable legislation and the maximum working pressure of the unit
(see "PS High" on the unit name plate), larger piping thickness might be required.
Use polyethylene foam as insulation material:
-
with a heat transfer rate between 0.041 and 0.052  W/mK (0.035 and
0.045 kcal/mh°C)
-
with a heat resistance of at least 120°C
Insulation thickness
Pipe outer diameter (Ø
6.4 mm (1/4")
15.9 mm (5/8")
Ø
Ø
i
i
Ø
Ø
p
p
t
If the temperature is higher than 30°C and the humidity is higher than RH 80%, the
thickness of the insulation materials should be at least 20  mm to prevent
condensation on the surface of the insulation.
NOTICE
The unit is only to be used in a closed water system. Application in an open water
circuit can lead to excessive corrosion of the water piping.
 6].
Ø6.4 mm (1/4")
Ø15.9 mm (5/8")
Temper grade
Annealed (O)
≥0.8 mm
Annealed (O)
≥1.0 mm
) Insulation inner diameter
p
)
i
8~10 mm
16~20 mm
EVLQ05+08CAV3 + EHYHBH05AF + EHYHBH/X08AF + EHYKOMB33AA
"1  General safety
(a)
Thickness (t)
Insulation thickness (t)
10 mm
13 mm
Daikin Altherma hybrid heat pump
4P355634-1F – 2020.10
Ø
t