Installation and operation manual
Daikin Altherma hybrid heat pump – gas boiler
module
Installation and operation manual
English
Daikin Altherma hybrid heat pump – gas boiler module
EHYKOMB33AA

Advertisement

Table of Contents
loading

Summary of Contents for Daikin EHYKOMB33AA

  • Page 1 Installation and operation manual Daikin Altherma hybrid heat pump – gas boiler module Installation and operation manual English Daikin Altherma hybrid heat pump – gas boiler module EHYKOMB33AA...
  • Page 2 AD130276­1...
  • Page 3: Table Of Contents

    Plume management kit ..........21 Benchmark  Checklist  can  be  used  to  demonstrate  compliance  with 7.7.11 Flues in voids .............. 22 Building  Regulations  and  should  be  provided  to  the  customer  for Finishing the gas boiler installation..........22 future reference. 7.8.1 To close the gas boiler..........22 7.8.2 To install the cover plate ..........22 EHYKOMB33AA Installation and operation manual Daikin Altherma hybrid heat pump – gas boiler module 4P353067­1A – 2013.10...
  • Page 4: About The Documentation

    Scheme.  Visit  http:// installation www.centralheating.co.uk for more information. manual Approvals Outdoor unit Installation instructions Paper (in the box of the installation outdoor unit) British Gas Service listing: manual EHYKOMB33AA: G.C.N. 47­464­01 Installer Preparation of the Digital files on http:// The product (hybrid system) combines the following 2 parts: reference installation, technical www.daikineurope.com/ guide specifications, reference support­and­manuals/ ▪ heat pump module, data,… product­information/. ▪ gas boiler module. Addendum Additional info about how Paper (in the box of the The modules MUST always be installed and used together.
  • Page 5: For The Installer

    ▪ Do NOT sit, climb or stand on the unit. Using filling water and top­up water which does NOT meet the stated In  accordance  with  the  applicable  legislation,  it  might  be  necessary quality  requirements  can  cause  a  considerably  reduced  service  life to provide a logbook with the product containing at least: information of  the  equipment.  The  responsibility  for  this  is  entirely  that  of  the on maintenance, repair work, results of tests, stand­by periods,… user. EHYKOMB33AA Installation and operation manual Daikin Altherma hybrid heat pump – gas boiler module 4P353067­1A – 2013.10...
  • Page 6: Electrical

    ▪ the  type  of  gas  quoted  on  the  type  identification  plate  or  on  the Building  Standards  (Scotland),  I.S.813  Installation  of  Gas setting type identification plate, Appliances  (Ireland),  IEE  Wiring  Regulations  (BS  7671),  Health ▪ the quitted gas pressure. and  Safety  Document  No.  635  (Electricity  at  Work  Regulations) Operate the unit ONLY with the gas type and gas pressure indicated and Local Water Authority Bye Laws on these type identification plates. ▪ UK Water Regulations and Bye Laws ▪ Health & Safety Installation and operation manual EHYKOMB33AA Daikin Altherma hybrid heat pump – gas boiler module 4P353067­1A – 2013.10...
  • Page 7: About The Box

    Potable  water:  all  seals,  joints  and  compounds  (including  flux  and solder)  and  components  used  as  part  of  the  secondary  domestic water system MUST be approved by WRAS. About the box Gas boiler 4.1.1 To unpack the gas boiler ALWAYS move the gas boiler in the original delivery packaging to its nearest installation position. WARNING Tear apart and throw away plastic packaging bags so that nobody,  especially  children,  can  play  with  them.  Possible risk: suffocation. EHYKOMB33AA Installation and operation manual Daikin Altherma hybrid heat pump – gas boiler module 4P353067­1A – 2013.10...
  • Page 8: To Remove The Accessories From The Gas Boiler

    7,8 - 27,1 Tmax °C and options ~230V-50Hz, 105W, IP44 0063 2013 5.2.1 List of options for gas boiler Accessories Part number Description EKFGP6837 Roof terminal PP/GLV 60/100 AR460 EKFGS0518 Weather slate steep Pb/GLV 60/100 18°­22° EKFGS0519 Weather slate steep Pb/GLV 60/100 23°­17° EKFGP7910 Weather slate steep PF 60/100 25°­45° EKFGS0523 Weather slate steep Pb/GLV 60/100 43°­47° EKFGS0524 Weather slate steep Pb/GLV 60/100 48°­52° EKFGS0525 Weather slate steep Pb/GLV 60/100 53°­57° Installation and operation manual EHYKOMB33AA Daikin Altherma hybrid heat pump – gas boiler module 4P353067­1A – 2013.10...
  • Page 9 EKFGT6307 Weather slate steep Pb/GLV 80/125 53°­57° EKFGP1284 PMK elbow 60 90 (UK only) EKFGP1297 Weather slate flat aluminum 80/125 0°­15° EKFGP1285 PMK elbow 60 45° (2 pieces) (UK only) EKFGP6368 Tee flex 100 boiler connection set 1 EKFGP1286 PMK extension 60 L=1000 includes bracket (UK only) EKFGP6354 Flex 100­60 + support elbow EKHY075787 Propane set EKHY090717 Concentric connection set 80/125 EKFGP6215 Tee flex 130 boiler connection set 1 EKHY90707 Dual pipe conversion set EKFGS0257 Flex 130­60 + support elbow EKHY093467 Cover plate for boiler EKFGW5333 Weather slate flat aluminum 80/125 EHYKOMB33AA Installation and operation manual Daikin Altherma hybrid heat pump – gas boiler module 4P353067­1A – 2013.10...
  • Page 10: Preparation

    EKFGP6324 Connector­flex­flex PP 80 EKFGP6347 Extension flex PP 100 L=25 m EKFGP6333 Spacer PP 80­100 EKFGP4481 Fixation Ø100 EKFGP6325 Connector flex­flex PP 100 EKFGP5197 Chimney top PP 130 with Preparation included flue pipe Preparing the gas boiler EKFGS0252 Adapter flex­fixed PP 130 installation Make sure that the hydrobox is already mounted to the wall. EKFGP6353 Support bracket top inox Ø130 EKFGS0250 Extension flex PP 130 L=130 m EKFGP6366 Connector flex­flex PP 130 It is recommended to first install: EKFGP1856 Flex kit PP Ø60­80 ▪ the water piping, ▪ the refrigerant piping, ▪ the electrical connection to the heat pump module. EKFGP4678 Chimney connection 60/100 Installation and operation manual EHYKOMB33AA Daikin Altherma hybrid heat pump – gas boiler module 4P353067­1A – 2013.10...
  • Page 11: Installation

    2 Unscrew both screws. 3 Tilt the front panel towards you and remove the front panel. 7.1.2 To open the switch box cover of the gas boiler 1 Open  the  gas  boiler,  see  "7.1.1  To  open  the  gas  boiler"  on page 11. 2 Pull the boiler controller unit forwards. The boiler controller will tip downwards to provide access. 6 Slide  the  boiler  downwards  to  fix  the  boiler  bracket  onto  the indoor unit mounting bracket. EHYKOMB33AA Installation and operation manual Daikin Altherma hybrid heat pump – gas boiler module 4P353067­1A – 2013.10...
  • Page 12: To Install The Condensate Trap

    The  discharge duct  MUST  have  a  minimum  gradient  of  5~20  mm/m. Condensate discharge via the gutter is NOT allowed due to risk of frost and the possible damage to the materials. 4 Connect  the  flexible  tube  (where  applicable  with  the  overflow pipe  from  the  pressure  relief  valve)  to  the  drain  via  an  open connection. Installation and operation manual EHYKOMB33AA Daikin Altherma hybrid heat pump – gas boiler module 4P353067­1A – 2013.10...
  • Page 13: Internal Connections

    The  pump  outlet  pipe  should  discharge  to  a  suitable  internal  foul water  discharge  point  such  as  an  internal  soil  and  vent  stack, internal  kitchen,  bathroom  waste  pipe,  or  washing  machine  waste pipe. A suitable permanent connection to the foul waste pipe should be used. Domestic hot water outlet Cold water inlet Pressure relief valve (field supply) 2 Install a pressure relief valve. 3 Connect the hot water connection (Ø15 mm). EHYKOMB33AA Installation and operation manual Daikin Altherma hybrid heat pump – gas boiler module 4P353067­1A – 2013.10...
  • Page 14: To Fill The Space Heating Circuit

    4 Make  sure  that  the  air  purge  valves  of  the  gas  boiler  and  the 1 The space heating piping of the boiler will be connected to the heat pump module are open (at least 2 turns). indoor unit. 5 Fill  the  circuit  with  water  until  the  boiler  display  indicates  a 2 Install  the  straight  brass  fitting  connections  so  that  they pressure of ±2 bar (with a minimum of 0.5 bar). perfectly match the connection of both modules. 6 Purge air from the water circuit as much as possible. 3 Tighten the straight brass fitting connections. 7 Disconnect the water supply hose from the drain point. Installation and operation manual EHYKOMB33AA Daikin Altherma hybrid heat pump – gas boiler module 4P353067­1A – 2013.10...
  • Page 15: Connecting The Electrical Wiring

    5 Plug  the  gas  boiler  connector  into  connector  X5  of  the  gas boiler PCB. Make sure the solenoid coil is outside the gas boiler CAUTION switch box. For  installation  in  damp  rooms,  a  fixed  connection  is obligatory. When working on the electrical circuit ALWAYS isolate the electric supply. 6 Route  the  communication  cable  from  the  gas  boiler  to  the indoor unit as in figure below. EHYKOMB33AA Installation and operation manual Daikin Altherma hybrid heat pump – gas boiler module 4P353067­1A – 2013.10...
  • Page 16: Connecting The Gas Piping

    4 Fit  the  concentric  pipe  for  the  air  supply  and  combustion  gas flue  into  the  adapter.  The  integral  sealing  ring  ensures  an airtight connection. 5 Check  the  connection  of  the  internal  flue  pipe  and  the condensate collector. Make sure it is properly connected. 2 Install a gas mesh filter in the gas connection if the gas may be contaminated. 3 Connect the gas boiler to the gas supply. Installation and operation manual EHYKOMB33AA Daikin Altherma hybrid heat pump – gas boiler module 4P353067­1A – 2013.10...
  • Page 17: To Change The 60/100 Concentric Connection To A Dual Pipe Connection

    5 Check  the  connection  of  the  internal  flue  pipe  and  the condensate collector. Make sure it is properly connected. For a dual pipe connection, all defined lengths assume a diameter of 80 mm. In case of smaller or larger pipe diameters, the permissible pipe  length  is  respectively  smaller  or  larger.  In  case  of  smaller diameter, the following applies: ▪ Ø70: 0.59 × the permissible pipe length for Ø80 ▪ Ø60: 0.32 × the permissible pipe length for Ø80 ▪ Ø50: 0.15 × the permissible pipe length for Ø80 Contact the manufacturer to check the calculations for the resistance of  the  air  supply  and  combustion  gas  flue  pipe  and  the  wall temperature at the end of the combustion gas flue pipe. EHYKOMB33AA Installation and operation manual Daikin Altherma hybrid heat pump – gas boiler module 4P353067­1A – 2013.10...
  • Page 18: Appliance Categories And Pipe Lengths

    L1+L2+L3+(2×2) m 13 m Air supply L4+L5+L6+(2×2) m 12 m Total  piping  length  =  sum  of  the  straight  pipe  lengths  +  sum  of  the L2=–1.8×L1+11.8 equivalent pipe length of bends/elbows. 7.7.4 Appliance categories and pipe lengths Following installation methods are supported by the manufacturer. Single boiler installation INFORMATION All  piping  lengths  in  the  tables  below  are  maximum equivalent piping lengths. Installation and operation manual EHYKOMB33AA Daikin Altherma hybrid heat pump – gas boiler module 4P353067­1A – 2013.10...
  • Page 19 Twin­80 60/100 80/125 Twin­80 L1+L2 (m) L1 (m) L1 (m) L1+L2 (m) Special  remark  regarding  C :  Refer  to  the  table  below  for  the minimum diameters of the combined gas exhaust system. Number of units Minimum Ø Special  remark  regarding  C :  Refer  to  the  table  below  for  the minimum diameters of the combined gas exhaust/air intake system. EHYKOMB33AA Installation and operation manual Daikin Altherma hybrid heat pump – gas boiler module 4P353067­1A – 2013.10...
  • Page 20: Applicable Materials

    From an opening in a car port (e.g. door, window) into a dwelling Vertically from a terminal on the same 1500 wall Horizontally from a terminal on the same wall Above an opening, air brick, opening windows, etc. Horizontally to an opening, air brick, opening windows, etc. Above roof level (to base terminal) From an adjacent wall to flue From an adjacent opening window 1000 From another roof terminal ­ From an external boundary. Note: If the terminal is facing a boundary, it is recommended that an anti­plume kit be fitted. Terminals adjacent to windows or openings on pitched and flat roofs: The 2000 flue should NOT penetrate this area. NOTICE The  boiler  manufacturer  cannot  be  held  responsible  for atmospheric conditions when siting flue terminals. Installation and operation manual EHYKOMB33AA Daikin Altherma hybrid heat pump – gas boiler module 4P353067­1A – 2013.10...
  • Page 21: Insulation Of The Gas Exhaust And Air Intake

    Flexible  flue  gas  lines  may  NOT  be  used  in  horizontal watertight. connection sections. ▪ Make sure that the flue system has a uniform gradient back to the boiler. 7.7.9 Fitting a vertical flue system A  vertical  60/100  mm  flue  kit  is  also  available.  By  using  additional components  available  from  your  boiler  supplier,  the  kit  can  be extended up to a maximum length as specified in the table indicating the maximum pipe lengths (excluding the initial boiler connection). CAUTION Read the installation manuals of the field supplied parts. EHYKOMB33AA Installation and operation manual Daikin Altherma hybrid heat pump – gas boiler module 4P353067­1A – 2013.10...
  • Page 22: Flues In Voids

    ▪ All  parts  of  the  flue  can  be  visually  inspected.  Ensure  suitable access where flue is positioned within voids. Finishing the gas boiler Gas boiler installation 8.1.1 Overview: Configuration 7.8.1 To close the gas boiler 1 Hook the top of the front panel into the top of the gas boiler. Read out On/off Main display Space heating operation Domestic hot water operation Domestic hot water comfort function eco Domestic hot water comfort function on (continuous) Service display Flashes to indicate a fault Operation On/off button  button  button Domestic hot water function off/eco/on Service button Reset button 2 Tilt the bottom side of the front panel towards the gas boiler. 3 Screw both screws of the cover. 4 Close the display cover. Installation and operation manual EHYKOMB33AA Daikin Altherma hybrid heat pump – gas boiler module 4P353067­1A – 2013.10...
  • Page 23: Basic Configuration

    In  case  of  heating  only  models,  this  function  can  be  deactivated through the parameter settings of the gas boiler. INFORMATION Do NOT deactivate the keep hot function if the gas boiler is connected to a reversible indoor unit. It is recommended to always deactivate the keep hot function if the gas boiler is connected to a heating only indoor unit. Frost protection function The  boiler  is  equipped  with  an  internal  frost  protection  function  that automatically  operates  when  necessary,  even  if  the  boiler  is  turned off. If the heat exchanger temperature drops too low, the burner will switch on until the temperature is sufficiently high again. When frost protection is active,   is displayed on the service display. EHYKOMB33AA Installation and operation manual Daikin Altherma hybrid heat pump – gas boiler module 4P353067­1A – 2013.10...
  • Page 24 ▪ 2=Powered  during  every  heat  demand  (space heating, domestic hot water, eco/comfort) ▪ 3=Zone regulation Booster Changing this setting has no effect on the operation of the unit. Step modulation ▪ 0=OFF during space heating operation ▪ 1=ON during space heating operation It is recommended not to modify this setting. Minimal space heating rpm 23%~50% Adjustment range 23~50% (40=propane). It is recommended not to modify this setting in case of natural gas. Minimal domestic hot water rpm 23%~50% Adjustment range 23~50% (40=propane). It is recommended not to modify this setting in case of natural gas. Minimal supply temperature during 10°C~16°C 40°C Changing this setting has no effect on the OT demand. (OpenTherm operation of the unit. thermostat) Installation and operation manual EHYKOMB33AA Daikin Altherma hybrid heat pump – gas boiler module 4P353067­1A – 2013.10...
  • Page 25 The  boiler  is  equipped  with  an  internal  frost  protection  function  that automatically  operates  when  necessary,  even  if  the  boiler  is  turned 8 Check  the  gas  connections  before  the  gas  valve  for off. If the heat exchanger temperature drops too low, the burner will gastightness. switch on until the temperature is sufficiently high again. When frost 9 Switch on the mains power. protection is active,   is displayed on the service display. 10 Check the gas connections after the gas valve for gastightness (during operation). 11 Now check the setting of the CO  percentage at high setting ( in display) and low setting (  in display). EHYKOMB33AA Installation and operation manual Daikin Altherma hybrid heat pump – gas boiler module 4P353067­1A – 2013.10...
  • Page 26 3 Remove the front panel from the gas boiler. Belgium) 4 Remove  the  sampling  point  (a)  and  insert  a  suitable  flue  gas Maximum value analyser probe. Minimum value  value at maximum power recorded at High setting. 11 If  the  CO   percentage  at  maximum  and  minimum  power  is within the range expressed in the tables above, the CO  setting of the boiler is correct. If NOT, adjust the CO  setting according to the instructions in the chapter below. Installation and operation manual EHYKOMB33AA Daikin Altherma hybrid heat pump – gas boiler module 4P353067­1A – 2013.10...
  • Page 27: Operation

    The  gas  boiler  has  an  electronic  boiler  controller  which  does  the the  gas  valve  should  be  made  without  prior  permission  of following when heating or hot water supply is required: your  local  Daikin  dealer.  In  Belgium  it  is  NOT  allowed  to adjust  the  gas  valve  and/or  break  its  seal.  Contact  your ▪ starting the fan, dealer.
  • Page 28: 10 Commissioning

    The  space  heating  supply  temperature  must  be  set  on  the  user will end automatically after 10 minutes. To perform a test run, switch interface  of  the  hybrid  module.  See  the  user  reference  guide  for off the system with the user interface. more details. Make sure the user interface shows the home screens and that the space heating and domestic hot water demands are turned off. There may be no error on the gas boiler or the heat pump module. During  a  gas  boiler  test  run,  "busy"  will  be  displayed  on  the  user interface. Installation and operation manual EHYKOMB33AA Daikin Altherma hybrid heat pump – gas boiler module 4P353067­1A – 2013.10...
  • Page 29: 11 Maintenance And Service

    11.2 To disassemble the gas boiler 1 Turn off the appliance. 2 Turn off the main power supply of the appliance. 3 Close the gas tap. 4 Remove the front panel. 5 Wait until the appliance has cooled down. 6 Unscrew the coupling nut at the base of the flue pipe by turning counterclockwise. 8 Pull  the  bottom  of  the  pipe  forwards  and  remove  the  pipe downwards  by  turning  the  pipe  alternately  clockwise  and counterclockwise. EHYKOMB33AA Installation and operation manual Daikin Altherma hybrid heat pump – gas boiler module 4P353067­1A – 2013.10...
  • Page 30: To Clean The Inside Of The Gas Boiler

    14 Unscrew  the  socket  head  screws  from  the  front  cover  and remove the socket complete with gas valve and fan to the front. NOTICE Make sure that the burner, insulation plate, gas valve, gas supply and fan do NOT get damaged. 11.3 To clean the inside of the gas 10 Turn it to the right with the condensate trap connection over the boiler edge of the base tray. 1 Clean  the  heat  exchanger  from  top  to  bottom  with  a  plastic brush or compressed air. 2 Clean the underside of the heat exchanger. 3 Clean the condensate drain pan with water. 4 Clean the condensate trap with water. Installation and operation manual EHYKOMB33AA Daikin Altherma hybrid heat pump – gas boiler module 4P353067­1A – 2013.10...
  • Page 31: To Assemble The Gas Boiler

    NEVER  bridge  safety  devices  or  change their  values  to  a  value  other  than  the  factory  default setting.  If  you  are  unable  to  find  the  cause  of  the problem, call your dealer. DANGER: RISK OF ELECTROCUTION EHYKOMB33AA Installation and operation manual Daikin Altherma hybrid heat pump – gas boiler module 4P353067­1A – 2013.10...
  • Page 32: Solving Problems Based On Symptoms

    ▪ Check  the  ignition  electrode setting is incorrect. interface and adjust if necessary. gap. Temperature is too low. Increase the space heating Gas/air adjustment NOT correctly Check the setting. See "To check temperature. set. the carbon dioxide setting" on No circulation in the installation. Check whether there is page 26. circulation. At least 2 or 3 Weak spark. Check the ignition gap. radiators MUST be open. Replace the ignition electrode. The boiler power has NOT been Adjust the power. See "Maximum Replace the ignition unit on the correctly set for the installation. space heating power setting" on gas valve. page 25. No heat transfer as a result of Descale or flush the heat lime scale or fouling in the heat exchanger on the space heating exchanger. side. Spark gap (±4.5 mm) Installation and operation manual EHYKOMB33AA Daikin Altherma hybrid heat pump – gas boiler module 4P353067­1A – 2013.10...
  • Page 33: Symptom: No Domestic Hot Water

    12.3.1 Error codes: Overview ▪ Replace fan Error codes of the gas boiler 29, 30 Gas valve relay Replace boiler controller fault The controller on the gas boiler detects faults and indicates them on the display by error codes. If  the  LED  is  flashing,  the  controller  has  detected  a  problem.  Once the  problem  is  rectified,  the  controller  can  be  restarted  by  pressing the   button. EHYKOMB33AA Installation and operation manual Daikin Altherma hybrid heat pump – gas boiler module 4P353067­1A – 2013.10...
  • Page 34: 13 Glossary

    Equipment  made  or  approved  by  Daikin  that  can  be combined  with  the  product  according  to  the  instructions  in the accompanying documentation. Field supply Equipment  not  made  by  Daikin  that  can  be  combined  with the  product  according  to  the  instructions  in  the accompanying documentation. Installation and operation manual EHYKOMB33AA Daikin Altherma hybrid heat pump – gas boiler module...
  • Page 35: 14 Technical Data

    14 Technical data Technical data 14.1 Components 14.1.1 Components: Gas boiler Gas valve Connection block/terminal strip X4 Boiler control panel Condensate drain pan Sensor S1 Hot water sensor S3 Sensor S2 Condensate S3 Heat exchanger Flow sensor Operating panel and read­out Space heating pressure sensor Ionisation/ignition electrode Mains lead 230 V AC without plug (stripped) Position of data plate Manual air bleed Sight glass Air supply cap Flue pipe adapter (use ONLY in combination with the accompanying elbow in flue sets) EHYKOMB33AA Installation and operation manual Daikin Altherma hybrid heat pump – gas boiler module 4P353067­1A – 2013.10...
  • Page 36: Wiring Diagram

    X2 X1 (230 V~) (230 V~) 3.15 3-4= 1= 0 V 2-3= 2= 24 V= 3= Tacho 4= Pwm Earth connections heat exchanger Spark plug cover Boiler controller Earth connections boiler controller Fuse (3.15 A T) Gas valve and ignition unit Ionisation/ignition probe Main voltage Flow sensor Return sensor Domestic hot water sensor Flow switch Space heating water pressure sensor Gas valve and ignition electrode Main power supply (2=l (BRN), 4=N (BLU)) Power supply fan (230 V) Boiler communication cable Sensor connection Installation and operation manual EHYKOMB33AA Daikin Altherma hybrid heat pump – gas boiler module 4P353067­1A – 2013.10...
  • Page 37: Technical Specifications

    14 Technical data 14.3 Technical specifications 14.3.1 Technical specifications: Gas boiler EHYKOMB33AA Operation range 15~80°C EHYKOMB33AA Domestic hot water Function Heating only Heating power domestic hot water 7.6~32.7 kW Heat pump module EHYHBH05 Efficiency domestic hot water (net 105% EHYHBH08 calorific value) Device category C13, C33, C43, C53, C63, Operation range 40~65°C C83, C93 Domestic hot water flow rate (setpoint 9 l/min Destination country – Gas supply GB – G20 (20 mbar), 60°C) pressure G31 (30~37 mbar) Domestic hot water flow rate (setpoint 15 l/min 40°C) FR – G20 (20 mbar), Casing G25 (25 mbar), Colour White – RAL9010 G31 (30 mbar)
  • Page 38 Déclaration de conformité A.R. 17/7/2009-BE Verklaring van overeenstemming K.B. 17/7/2009-BE Konformitätserklarung K.E. 17.7.2009-BE Daikin Europe N.V. Zandvoordestraat 300 B-8400 Oostende, Belgium Nous certifions par la présente que la série des appareils spécifiée ci-après est conforme au modèle type décrit dans la déclaration de conformité...
  • Page 39: Gas Boiler System Commissioning Checklist

    *All installations in England and Wales must be notified to Local Authority Building Control (LABC) either directly or through a Competent Persons Scheme. A Building Regulations Compliance Certificate will then be issued to the customer. ©Heating and Hotwater Industry Council (HHIC) www.centralheating.co.uk EHYKOMB33AA Installation and operation manual Daikin Altherma hybrid heat pump – gas boiler module 4P353067­1A – 2013.10...
  • Page 40 Gas Safe Register No. Comments: Comments: Signature: Signature: Service 9 Service 10 Date: Date: Engineer Name: Engineer Name: Company Name: Company Name: Telephone No. Telephone No. Gas Safe Register No. Gas Safe Register No. Comments: Comments: Signature: Signature: Installation and operation manual EHYKOMB33AA Daikin Altherma hybrid heat pump – gas boiler module 4P353067­1A – 2013.10...
  • Page 44 4P353067­1A  2013.10...