Configuration
Installer reference guide
142
#
N/A
[8-06]
INFORMATION
When leaving water temperature modulation is enabled, the weather‑dependent
curve needs to be set to a higher position than [8-06] plus the minimum leaving
water temperature setpoint required to reach a stable condition on the comfort
setpoint for the room. To increase efficiency, modulation can lower the leaving water
setpoint. By setting the weather‑dependent curve to a higher position, it cannot drop
below the minimum setpoint. See the illustration below.
T t
+[8-06]
−[8-06]
a Weather-dependent curve
b Minimum leaving water temperature setpoint required to reach a stable condition
on the comfort setpoint for the room.
Leaving water temperature: Emitter type
Only applicable in case of room thermostat control. Depending on the system
water volume and the heat emitters type, the heat up or cool down of a space can
take longer. This setting can compensate for a slow or a quick heating/cooling
system during the heat up/cool down cycle.
Note: The setting of the emitter type will influence the maximum modulation of
the desired leaving water temperature and the possibility for usage of the
automatic cooling/heating changeover based on the indoor ambient temperature.
Therefore it is important to set this correctly.
#
[A.3.1.1.7]
[9‑0B]
Quick heat up function
Only applicable in case of room thermostat control. The function will start up the
gas boiler when the actual room temperature is 3°C lower than the desired room
temperature. The large boiler capacity can boost up the room temperature quickly
to the desired temperature. This can be useful after a long period of absence or
after a break-down of the system. During the quick heat up function, the setpoint
of the gas boiler will be the maximum heating setpoint: [9‑00].
Code
Leaving water temperature maximum
modulation:
0°C~10°C (default: 5°C)
Requires modulation to be enabled.
This is the value by which the desired leaving
water temperature is increased or lowered.
a
b
T a
Code
Emitter type:
Reaction time of the system:
Quick (default) Example: Small water
volume, fan coils, or radiators.
Slow Example: Large water volume, floor
heating loops.
EVLQ05+08CAV3 + EHYHBH05AF + EHYHBH/X08AF + EHYKOMB33AA