To enable the power saving function setting, [E‑08] needs to be enabled on the
user interface in combination with the removal of the power saving connector at
the outdoor unit.
NOTICE
The power saving connector at the outdoor unit shall only be removed when the
main power supply to the application is switched OFF.
#
Code
N/A
[E‑08]
Power consumption control
Pwr consumpt. control
#
[A.6.3.1]
[4-08]
[A.6.3.2]
[4-09]
1 2 3
Power saving function for outdoor unit:
0: Disabled
1 (default): Enabled
Code
Mode:
0 (No limitation)(default): Disabled.
1 (Continuous): Enabled: You can set one
power limitation value (in A or kW) to which
the system power consumption will be
limited for all the time.
2 (Digital inputs): Enabled: You can set
up to four different power limitation values
(in A or kW) to which the system power
consumption will be limited when the
corresponding digital input asks.
Type:
0 (Current): The limitation values are set in
A.
1 (Power)(default): The limitation values are
set in kW.
EVLQ05+08CAV3 + EHYHBH05AF + EHYHBH/X08AF + EHYKOMB33AA