Daikin Altherma EVLQ05+08CA Installer's Reference Manual page 163

Hybrid heat pump
Hide thumbs Also See for Altherma EVLQ05+08CA:
Table of Contents

Advertisement

EVLQ05+08CAV3 + EHYHBH05AF + EHYHBH/X08AF + EHYKOMB33AA
Daikin Altherma hybrid heat pump
4P355634-1F – 2020.10
#
[A.6.3.3]
[5-05]
[A.6.3.4]
[5-09]
Amp. limits for DI: Only applicable in case of power limitation mode based
on digital inputs and based on current values.
[A.6.3.5.1]
[5-05]
[A.6.3.5.2]
[5-06]
[A.6.3.5.3]
[5-07]
[A.6.3.5.4]
[5-08]
kW limits for DI: Only applicable in case of power limitation mode based on
digital inputs and based on power values.
[A.6.3.6.1]
[5-09]
[A.6.3.6.2]
[5-0A]
[A.6.3.6.3]
[5-0B]
[A.6.3.6.4]
[5-0C]
Average timer
The average timer corrects the influence of ambient temperature variations. The
weather-dependent set point calculation is done on the average outdoor
temperature.
The outdoor temperature is averaged over the selected time period.
#
Code
[A.6.4]
[1-0A]
Code
Value: Only applicable in case of full time
power limitation mode.
0 A~50 A, step: 1 A (default: 50 A)
Value: Only applicable in case of full time
power limitation mode.
0 kW~20 kW, step: 0.5 kW (default: 20 kW)
Limit DI1
0 A~50 A, step: 1 A (default: 50 A)
Limit DI2
0 A~50 A, step: 1 A (default: 50 A)
Limit DI3
0 A~50 A, step: 1 A (default: 50 A)
Limit DI4
0 A~50 A, step: 1 A (default: 50 A)
Limit DI1
0 kW~20 kW, step: 0.5 kW (default: 20 kW)
Limit DI2
0 kW~20 kW, step: 0.5 kW (default: 20 kW)
Limit DI3
0 kW~20 kW, step: 0.5 kW (default: 20 kW)
Limit DI4
0 kW~20 kW, step: 0.5 kW (default: 20 kW)
Outdoor average timer:
0: No averaging
1: 12 hours (default)
2: 24 hours
3: 48 hours
4: 72 hours
8
Configuration
|
Description
Description
Installer reference guide
163