Daikin Altherma EVLQ05+08CA Installer's Reference Manual page 107

Hybrid heat pump
Hide thumbs Also See for Altherma EVLQ05+08CA:
Table of Contents

Advertisement

EVLQ05+08CAV3 + EHYHBH05AF + EHYHBH/X08AF + EHYKOMB33AA
Daikin Altherma hybrid heat pump
4P355634-1F – 2020.10
L2
L1
C
83
6
L2
L1
C
83
6
The horizontal flue MUST be installed under a 3° fall towards the boiler (50 mm per
metre) and MUST be supported with a minimum of 1 bracket at each meter length.
Best recommended position of the bracket is just before the joint.
INFORMATION
Flexible flue gas lines may NOT be used in horizontal connection sections.
INFORMATION
The maximum lengths in the table below apply to each gas boiler separately.
C
(6)
83
Twin-80
L1+L2 (m)
80
Special remark regarding C
the combined gas exhaust system.
Number of units
2
3
4
5
6
7
8
9
10
11
12
L1
L1
C
43
C
43
5
5
L1
L1
L2
C
43
C
43
5
5
60/100
L1 (m)
10
: See the table below for the minimum diameters of
83
7
Installation
|
C
(5)
43
80/125
Twin-80
L1 (m)
L1+L2 (m)
29
Minimum Ø
130
150
180
200
220
230
250
270
280
290
300
Installer reference guide
80
107