Activation Of Low Pressure Sensor - Daikin RXSQ24TAVJU Service Manual

60 hz
Hide thumbs Also See for RXSQ24TAVJU:
Table of Contents

Advertisement

SiUS331708EA

4.32 Activation of Low Pressure Sensor

E4
Error Code
Applicable
All outdoor units
Models
Method of Error
Abnormality is detected by the pressure value with the low pressure sensor.
Detection
Use the outdoor main PCB to determine the low pressure sensor pressure test value.
Error Decision
Error is generated when the low pressure drops below a specific pressure level.
Conditions
Low pressure drops after compressor activation.
Operating pressure: 0.07 MPa (10.2 psi)
Supposed
Causes
Service Diagnosis
Abnormal drop of low pressure
Defective low pressure sensor
Defective outdoor main PCB
Stop valve is not opened
Troubleshooting by Error Code
202