SiUS331708EA
Note that the control is automatically switched to the one performed only by the suction air thermistor for indoor
unit when the Second code No. is 01 during group control.
To use the remote controller thermistor during group control, select the Second code No. 02 in First code No. 6.
Mode No.
10 (20)
Note: When the 10(20)-6 setting is changed to 02, several indoor units are controlled by one remote
Filter Cleaning Sign
Whether or not to display "Filter Cleaning" after operation of certain duration can be selected.
Mode No.
10 (20)
∗ Filter cleaning sign is not displayed when an Auto-clean Panel is connected.
Information for intelligent Touch Manager / intelligent Touch Controller (for FXZQ-TA and FXSQ-TA models)
Mode No.
10 (20)
∗ When field setting 10 (20)-6-02 is set at the same time as 10 (20)-2-01,02,03, field setting 10 (20)-2 has priority.
When field setting 10 (20)-6-01 is set at the same time as 10 (20)-2-01,02,03, field setting 10 (20)-6 has priority
for group connection, and 10 (20)-2 has priority for individual connection.
Time for Absence Area Detection
(For units with the infrared presence/floor sensor only)
By selecting the energy-saving operation mode in the absence, the target temperature is shifted to the energy-
saving end by 1°C (maximum 2°C) after the state of absence continues for a certain period of time.
Absent time defined for detection can be selected as follows:
Mode No.
10 (20)
• The set temperature displayed on the remote controller remains same even if the target temperature is shifted.
• As soon as people is detected while the temperature is shifted, this control will be cancelled (reset).
Field Settings and Test Operation
First Code No. Second Code No.
01
6
02
controller thermistor, so note that the room temperature might be uneven.
First Code No.
3
First Code No.
5
First Code No.
7
31
30
29
28
27
26
21
20
19
18
17
Remote controller thermostat control is not permitted during group control.
Remote controller thermostat control is permitted during group control.
Second Code No.
01
02
Second Code No.
Only indoor unit sensor value (or remote controller
01
02
Sensor values according to 10 (20)-2 and 10 (20)-6.
Second Code No.
01
02
Human detection
State of absence
Cooling (at 28˚C)
Heating (at 20˚C)
30 (60)∗
60 (120)∗
Elapsed time of absence (min.)
∗ The values in parentheses represent the time
when Second code No. is "02."
Field Settings from Remote Controller
Contents
Contents
Displayed
Not displayed
Contents
sensor value, if installed.)
Contents
30 minutes
60 minutes