Daikin RXSQ24TAVJU Service Manual page 108

60 hz
Hide thumbs Also See for RXSQ24TAVJU:
Table of Contents

Advertisement

Field Settings from Remote Controller
FXTQ-TA, CXTQ-TA
Mode No.
10 (20)
When the Second Code No. is set to 02, room temperature is controlled by the remote sensor thermistor.
When the Second Code No. is set to 03, room temperature is controlled by the remote controller thermistor.
When the unit is equipped with an infrared presence/floor sensor:
Mode No.
10 (20)
11 (21)
The thermistor to be used
Remote controller thermistor
Suction air thermistor
Infrared presence/floor sensor
∗ Refer to Compensating the temperature around people on page 100.
95
First Code No.
2
(˚F)
(˚C)
96.8
36
93.2
34
89.6
32
86
30
82.4
28
78.8
26
75.2
24
71.6
22
68
20
17
19
62.6
66.2
(˚F)
(˚C)
89.6
32
86
30
82.4
28
78.8
26
In heating
75.2
24
71.6
22
68
20
64.4
18
60.8
16
57.2
14
14
57.2 60.8 64.4
First Code No.
2
01
8
01
The infrared
presence/floor
sensor is not used
Only the suction air
thermistor is used
Second Code No.
01
02
Remote sensor thermistor
03
Remote controller thermistor
In cooling
Suction air
Remote controller
thermistor
thermistor
Suction air
Remote controller
thermistor
thermistor
21
23
25
27
29
69.8 73.4
77
80.6 84.2 87.8 91.4
Suction air temperature
Suction air
Remote controller
thermistor
thermistor
Suction air
Remote controller
thermistor
thermistor
16
18
20
22
24
26
68
71.6 75.2 78.8 82.4
Suction air temperature
Second Code No.
02
02
01
02
Priority given to
the suction air
temperature (∗)
Standard setting
(Factory setting)
Contents
Suction air
thermistor
Suction air
thermistor
31
33
35
37
(˚C)
95
98.6
(˚F)
Suction air
thermistor
Suction air
thermistor
28
30
32
34
(˚C)
86
89.6 93.2
(˚F)
02
02
03
03
04
01
Priority given to the
floor temperature (∗)
Only the remote
controller thermistor
is used
Field Settings and Test Operation
SiUS331708EA