Daikin RXSQ24TAVJU Service Manual page 105

60 hz
Hide thumbs Also See for RXSQ24TAVJU:
Table of Contents

Advertisement

SiUS331708EA
Mode
First
No.
Code
(∗2)
No.
0
Setting of airflow rate
Airflow direction setting
1
(Set when a blocking pad kit has been installed.)
2 (∗9) Swing pattern settings
3 (∗13) Operation of downward flow flap
13(23)
4
Setting of airflow direction adjustment range
5 (∗10) CFM table setting
5 (∗12) Setting of static pressure selection
6
External static pressure settings
Optional kit setting (UV lamp + humidifier +
4 (∗11)
economizer)
5 (∗11) Residential dry
14
(24)
9 (∗13) Mold proof operation setting
11 (∗10) Gas furnace test mode
0
Drain pump operation settings
1
Humidification when heating thermostat is OFF
Setting of direct duct connection
(when the indoor unit and energy recovery
2
15(25)
ventilator unit are connected by duct directly.)
(∗5)
Interlocked operation between humidifier and
3
drain pump
5
Individual setting of ventilation
1b
3
Display of contact center
4
Display of error codes on the remote controller
12
Key-lock pattern settings
14
Setting "restricted / permitted" of airflow block
1c
0
Room temperature display
Notes :
1. Settings are made simultaneously for the entire group, however, if you select the mode No. inside
parentheses, you can also set by each individual unit. Setting changes however cannot be checked except in
the individual mode for those in parentheses.
∗2. The mode numbers inside parentheses cannot be used by wireless remote controllers, so they cannot be set
individually. Setting changes also cannot be checked.
3. Do not make settings other than those described above. Nothing is displayed for functions the indoor unit is
not equipped with.
4. 88 or Checking the connection. Please stand by. may be displayed to indicate the remote controller is
resetting when returning to the normal mode.
∗5. If the setting mode to "Equipped", energy recovery ventilator fan conducts the fan residual operation by
linking to indoor unit.
∗6. Only for FXTQ-TA models
∗7. Only for FXDQ-M, FXTQ-TA, CXTQ-TA models
∗8. If the airflow setting when thermostat is OFF is set to OFF (12(22)-3-03, 12(22)-6-03), the air in the indoor
unit will be stagnant and suction air thermistor may not detect room temperature correctly, resulting in
problems that thermostat will not be ON easily.
Use optional remote sensor in such conditions, or set the field setting 10(20)-2 to 03 (only remote controller
thermistor).
∗9. Only for FXFQ-T and FXUQ-P sensing models
∗10.Only for CXTQ-TA models
∗11.Only for FXTQ-TA and CXTQ-TA models
∗12.Only for FXDQ-M models
∗13.Only for FXEQ-P models
∗14.Only for FXZQ-TA and FXSQ-TA models
Field Settings and Test Operation
Setting Contents
Second Code No.
01
Refer to page 103 for details.
F (4 directions)
T (3 directions)
All direction
synchronized swing
Equipped
Not equipped
Draft prevention
Standard
Standard
Standard
High static pressure
Refer to page 105 for details.
Refer to page 106 for details.
Set temperature:
Set temperature:
same as cooling set
room temperature
temperature
For high humidity
Standard
areas
OFF
Low heat
Not equipped
Equipped
Not equipped
Equipped
Not interlocked
Interlocked
Not individual
Individual
Displayed
Not displayed
Two-digit display
No operation
No operation
allowed (Cancel
allowed (Cancel
procedure is
procedure is not
displayed.)
displayed.)
Refer to page 108 for details.
Room temperature
Room temperature
is not displayed
is displayed
Field Settings from Remote Controller
02
03
W
(2 directions)
Facing swing
Ceiling soiling
prevention
Low
High heat
ON
OFF
No menu
operation is
allowed
(Cancel
procedure is
displayed.)
04
Four-digit
display
No menu
operation is
allowed any
time.
92