Inverter Circuit Capacitor High Voltage - Daikin RXSQ24TAVJU Service Manual

60 hz
Hide thumbs Also See for RXSQ24TAVJU:
Table of Contents

Advertisement

Troubleshooting by Error Code

4.46 Inverter Circuit Capacitor High Voltage

P1
Error Code
Applicable
All outdoor units
Models
Method of Error
The voltage waveform of the main circuit capacitor of the inverter is used to check for errors.
Detection
Error Decision
The above-mentioned voltage waveform looks like the waveform of the power supply with a
Conditions
missing phase
Supposed
Causes
Troubleshooting
219
Defective main circuit capacitor
Incorrect main circuit wiring
Defective outdoor unit PCB
Unbalanced voltage between phases
Missing phase
Be sure to turn off the power switch before connecting or disconnecting
Caution
connectors, or parts may be damaged.
Measure voltage between L1 and L2,
L1 and L3, and L2 and L3.
Is three-phase power
voltage within rated voltage
±10%?
YES
Is the
unbalanced phasic voltage
within ±10%?
YES
NO
NO
SiUS331708EA
Calibrate the power voltage.
Calibrate the power voltage.
Replace the outdoor main
PCB (A1P).
Service Diagnosis

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Rxsq36tavjuRxsq48tavjuRxsq60tavju

Table of Contents