List Of Field Settings For Outdoor-Air Processing Unit; Setting Of Operation Control Mode - Daikin RXSQ24TAVJU Service Manual

60 hz
Hide thumbs Also See for RXSQ24TAVJU:
Table of Contents

Advertisement

SiUS331708EA
1.5

List of Field Settings for Outdoor-Air Processing Unit

First
Mode
Setting Contents
Code
No.
No.
0
Filter contamination
10
Display time to
(20)
3
clean air filter
calculation
External ON/OFF
1
input
12
(22)
Power failure
5
automatic reset
Discharge
pipe
3
temperature
(cooling)
14
(24)
Discharge
pipe
4
temperature
(heating)
1.6

Setting of Operation Control Mode

The operation control mode is compatible with a variety of controls and operations by limiting the functions of the
operation remote controller. Furthermore, operations such as remote controller ON/OFF can be limited in
accordance with the combination conditions. (Refer to information on the next page.)
Centralized remote controller is normally available for operations. (Except when centralized monitor is
connected)
1.6.1 Contents of Control Modes
20 modes consisting of combinations of the following 5 operation modes with temperature and operation mode
setting by remote controller can be set and displayed by operation modes 0 through 19.
ON/OFF control impossible by remote controller
Used when you want to turn ON/OFF by centralized remote controller only.
(Cannot be turned ON/OFF by remote controller.)
OFF control only possible by remote controller
Used when you want to turn on by centralized remote controller only, and off by remote controller only.
Centralized
Used when you want to turn on by centralized remote controller only, and turn on/off freely by remote
controller during set time.
Individual
Used when you want to turn ON/OFF by both centralized remote controller and remote controller.
Timer operation possible by remote controller
Used when you want to turn ON/OFF by remote controller during set time and you do not want to start
operation by centralized remote controller when time of system start is programmed.
Field Settings and Test Operation
01
02
2500 hr
1250 hr
No
Display
display
Forced
ON/OFF
OFF
control
Not
equipped Equipped
°C
13
14
°F
55.4
57.2
°C
18
19
°F
64.4
66.2
Second Code No.
03
04
05
06
07
15
16
17
18
19
59
60.8 62.6 64.4 66.2
20
21
22
23
24
68 69.8 71.6 73.4 75.2 77 78.8 80.6 82.4 84.2
Field Settings from Remote Controller
08
09
10
11
12
20
21
22
23
24
68
69.8 71.6 73.4 75.2
25
26
27
28
29
: The same value continues.
: Factory setting
13
14
15
25
25
25
77
77
77
30
30
30
86
86
86
110

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Rxsq36tavjuRxsq48tavjuRxsq60tavju

Table of Contents