Field Settings from Remote Controller
Setting of Airflow Rate
Make the following setting according to the ceiling height. The second code No. is set to 01 at the factory.
FXFQ07-24T, FXFQ09-30P, FXUQ18/24P
Mode No.
13 (23)
FXFQ30-48T, FXFQ36/48P, FXUQ30/36P
Mode No.
13 (23)
FXZQ-TA, FXEQ-P
Mode No.
13 (23)
FXHQ, FXAQ
Mode No.
13 (23)
Airflow Direction Setting
Set the airflow direction of indoor units as given in the table below. (Set when sealing material kit of air discharge
outlet has been installed.) The second code No. is factory set to 01.
Mode No.
13 (23)
103
First Code
Second
No.
Code No.
01
0
02
03
First Code
Second
No.
Code No.
01
0
02
03
First Code
Second
No.
Code No.
01
0
02
03
First Code No.
0
First Code No.
Second Code No.
1
Contents
4-way Outlets
Lower than
Standard
(8-3/4 ft)
Lower than
High Ceiling 1
(10 ft)
Lower than
Higher Ceiling 2
(11-1/2 ft)
Contents
4-way Outlets
Lower than
Standard
(10-1/2 ft)
Lower than
High Ceiling 1
(12 ft)
Lower than
Higher Ceiling 2
(13-3/4 ft)
Contents
Standard
High Ceiling 1
Higher Ceiling 2
Second Code No.
01
02
03
01
F: 4-direction airflow
02
T: 3-direction airflow
03
W: 2-direction airflow
Ceiling height
3-way Outlets
Lower than
2.7 m
3.0 m
(10 ft)
Lower than
3.0 m
3.3 m
(10-3/4 ft)
Lower than
3.5 m
3.5 m
(11-1/2 ft)
Ceiling height
3-way Outlets
Lower than
3.2 m
3.6 m
(12 ft)
Lower than
3.6 m
4.0 m
(13-1/8 ft)
Lower than
4.2 m
4.2 m
(13-3/4 ft)
Ceiling height
Lower than 2.7 m (8-3/4 ft)
Lower than 3.0 m (10 ft)
Lower than 3.5 m (11-1/2 ft)
Contents
Standard
Slight increase
Normal increase
Contents
Field Settings and Test Operation
SiUS331708EA
2-way Outlets
Lower than
3.5 m
(11-1/2 ft)
Lower than
3.8 m
(12-1/2 ft)
—
2-way Outlets
Lower than
4.2 m
(13-3/4 ft)
Lower than
4.2 m
(13-3/4 ft)
—