Wireless Remote Controller - Daikin RXSQ24TAVJU Service Manual

60 hz
Hide thumbs Also See for RXSQ24TAVJU:
Table of Contents

Advertisement

SiUS331708EA
3.2

Wireless Remote Controller

If the unit stops due to an error, the operation indicating LED on the signal receiving part of indoor unit blinks.
The error code can be determined by following the procedure described below. (The error code is displayed
when an operation error has occurred. In normal condition, the error code of the last problem is displayed.)
1. Press INSPECTION/TEST button to enter inspection mode. Then the figure 0 blinks on the unit number
display.
2. Press UP button or DOWN button and change the unit number until the receiver of the remote controller starts
to beep.
3 short beeps : Follow all steps below.
1 short beep : Follow steps 3 and 4. Continue the operation in step 4 until you hear a continuous beep. This
Continuous beep : There is no abnormality.
3. Press MODE button. The left 0 (upper digit) indication of the error code blinks.
4. Press UP button or DOWN button to change the error code upper digit until the receiver of the indoor unit
starts to beep.
The upper digit of the code changes as shown below.
Continuous beep : Both upper and lower digits match. (Error code is confirmed.)
2 short beeps : The upper digit matches but the lower digit does not.
1 short beep : The upper digit does not match.
5. Press MODE button. The right 0 (lower digit) indication of the error code blinks.
6. Press UP button or DOWN button and change the error code lower digit until the receiver of the indoor unit
generates a continuous beep.
Service Diagnosis
continuous beep indicates that the error code is confirmed.
O0 A C E H F J L P U 9 8 7 6 5 4
"UP" button
UP button
DOWN button
Unit number
MODE button
INSPECTION/TEST button
"DOWN" button
Service Check Function
150

Hide quick links: