Special Control
3.5

Restart Standby

Restart is forced into standby to prevent the power from frequently turning ON and OFF and to equalize pressure
in the refrigerant system.
Ta: Outdoor air temperature
Outdoor unit actuator
Compressor
Outdoor fan
Four way valve
Main electronic expansion
valve
Subcooling electronic
expansion valve
Hot gas bypass valve
Injection valve
Ending conditions
3.6

Stop Control

Actuator operation is cleared when the system is down.
Outdoor unit actuator
Compressor
Outdoor fan
Four way valve
Main electronic expansion
valve
Subcooling electronic
expansion valve
Hot gas bypass valve
Injection valve
Ending conditions
51
Electric symbol
24/36 class 48 class 60 class
M1C
M1C
M1C
OFF
M1F,
Ta > 30°C (86°F): STEP 4
M1F
M1F
Ta ≤ 30°C (86°F): OFF
M2F
Y1S
Y1S
Y1S
Holds
0 pulse
Y1E
Y1E
Y1E
Y3E
0 pulse
Y2S
ON
Y3S
Y3S
OFF
2 minutes
Electric symbol
24/36 class 48 class 60 class
M1C
M1C
M1C
OFF
M1F,
M1F
M1F
OFF
M2F
Y1S
Y1S
Y1S
Holds
Y1E
Y1E
Y1E
0 pulse
Y3E
0 pulse
Y2S
OFF
Y3S
Y3S
OFF
Indoor unit thermostat is turned ON.
Operation
Operation
Functions and Control
SiUS331708EA