Concept Of Inverter-Related Error Codes - Daikin RXSQ24TAVJU Service Manual

60 hz
Hide thumbs Also See for RXSQ24TAVJU:
Table of Contents

Advertisement

Check
5.9

Concept of Inverter-Related Error Codes

CHECK 10
Power supply
(Single phase, 208/230 VAC)
U2 P1
Imbalanced power supply voltage
When imbalance in
voltages among three
phases comes to 3%
or more
Power supply voltage error
When the power supply
voltage falls out of the range
of 208/230 VAC ± 10%
265
LC
Low voltage
part
High voltage part
(Power
transmission etc.)
L1
P4
Defective radiation fin thermistor
When the radiation fin thermistor resistor detects
an open circuit (–30˚C (–22˚F) or less) or a short
circuit (120˚C (248˚F) or more)
Defective radiation inverter
When the radiation heavy current part of
inverter gets defective (gives no output)
Outdoor
main
PCB
L5
L8
L4
Radiation fin temperature rise
When the radiation fin
temperature reached
87˚C (188˚F) or more
SiUS331708EA
Transmission error
When transmissions between the
microcomputers on the main
PCB are not normal
Instantaneous overcurrent of inverter
compressor (When inverter output current
exceeds 59.1 A even instantaneously)
Overcurrent of inverter compressor
(1) A current of 33.5 A or more
continues for a period of
consecutive 5 seconds.
(2) A current of 27.6 A or more
continues for a period of
consecutive 260 seconds.
E5
L9
Defective startup of inverter compressor
(Compressor stops running
immediately after it starts up.)
Inverter compressor lock
(Compressor does not run at all.)
Service Diagnosis

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Rxsq36tavjuRxsq48tavjuRxsq60tavju

Table of Contents