Analog Output Module Command - Advantech ADAM 4000 Series User Manual

Data acquisition modules
Hide thumbs Also See for ADAM 4000 Series:
Table of Contents

Advertisement

4021

4.5 Analog Output Module Command

Command Syntax
%AANNTTCCFF
#AA(data)
$AA4
$AA3 (number of
counts)
$AA0
$AA1
$AA2
$AA6
$AA8
$AA5
$AAF
$AAM
Command Name
Configuration
Sets the address, output range, baud
rate, data format, slew rate and/or
checksum status
Analog Data Out
Directs output data to a specified
module
Start-Up Output
Stores a default output value in a
Current or
specified module. The output value
Voltage
will take effect upon startup
Configuration
Trim Calibration
Trims specified module a number of
units up/down
4 mA Calibration
Tells the module to store parameters
for 4mA Calibration
20 mA Calibration Tells the module to store parameters
for 20 mA Calibration
Configuration
Reads the configuration of specified
Status
module
Last Value
Returns either last value sent to
Readback
specified module by #AA command, or
start-up output current/voltage
Current Readback Returns measured value of the
current/voltage flowing through
current loop
Reset Status
Checks if module has been reset since
the last $AA5 command
Read Firmware
Returns the firmware version code
Version
from the specified analog output
module
Read Model
Return the module name from
Name
specified analog output module
Description
Chapter 4 Command Set
4
Chapter
I/O
Module
4021
4021
4021
4021
4021
4021
4021
4021
4021
4021
4021
4021
4-127

Hide quick links:

Advertisement

Table of Contents
loading