Adam-4080 Counter/Frequency Input Module - Advantech ADAM 4000 Series User Manual

Data acquisition modules
Hide thumbs Also See for ADAM 4000 Series:
Table of Contents

Advertisement

Technical specifications
A.15 ADAM-4080 Counter/Frequency Input Module
Table A-19 ADAM-4080 Specifications
Input channels
Input frequency
Input mode
Isolation input level
Logic level 0
Logical level 1
Isolation voltage
Non-isolation input level Programmable threshold
Logic Ievel 0
Logic level 1
Input pulse width
Maximum count
Programmable digital
noise filter
Alarming
Preset type
Frequency measurement
Range
Programmable built-in
gate time
Digital output channels 2 channels open collector to 30 V
Sink current
Power dissipation
Watchdog timer
Power requirements
Power consumption
A-34
ADAM 4000 Series User's Manual
Two independent 32-bit counters
50 kHz max.
Isolated or non-isolated
+1 V max
+3.5 V to +30 V
2500 V
RMS
0 to +5 V (default = 0.8 V)
0 to +5 V (default = 2.4 V)
>10 µsec
4,294,967,295 (32 bits)
2 µsec to 65 msec
Alarm comparators on each counter
Absolute or relative
5 Hz to 50 KHz
1.0/0.1 sec
30 mA max. load
300 mW
Yes
+10 to +30 V
(non-regulated)
DC
2.0 W

Hide quick links: