D.2 ADAM-4018M Utility Software
The ADAM-4018M is designed to add memory to the ADAM-4018. To
simplify matters, it uses the same software utility as the ADAM-4018, but
with a few additional memory function settings:
Configuration setting
Alarm setting
Operation setting
Data reading
The following text provides a brief introduction on software usage.
Configuration setting
The configuration setting allows you to set the sampling interval, standal-
one mode, data logger mode and channel enable/disable status. The
sampling interval can be set from 2 to 65,535 seconds. To operate the
ADAM-4018M in the field, you must power on the memory module by
setting the standalone mode as "YES". Otherwise, the data will not be
recorded.
There are three data logging modes.
1. Standard Mode: All eight channels serve as the standard logger to
record normal data according to the sampling interval.
2. Event Mode: All eight channels serve as the event logger in cases when
the data recording value either exceeds the High Alarm limit or goes
below the Low Alarm limit.
3.Mixed Mode: Channels 0-3 serve as the standard logger, while channels
4-7 serve as the event logger.
NOTE For channel setting, "E" means Enable the channel to record data,
"D" means to Disable.