Installation 3. Wiring
1 Applicable electric wire
The following table shows applicable electric wire sizes . (Wire coating stripping length:10 to 11mm)
Section
Auxiliary power,
voltage input,
®
MODBUS
RTU
communication terminal
Current input terminal
Option terminal
Note :When using the bar terminal for insert 2 wire, please select insertion length of 12 to 13mm.
2 Connection method
①Peel the cover of the electric wire tip or crimp the bar terminal.
②With the lever pressed, insert the electric wire and then release the lever for connection.
■Example of the main unit
3 Checking
Check the following after connection.
□The electric wire is securely connected.
□There is no error in connection.
Screw type
Without screw
Without screw
Without screw
10 to 11mm
Electric wire
Insert hole
Lever
Specification of wire used
Single wire, Stranded wire: AWG24 to 14
(Stranded wire is bar terminal can be used in combination.)
Note: UL recognized corresponds, use according to the
following conditions.
・Single wire, Stranded wire: AWG24 to 18
・Bar terminal can be not used in combination.
Single wire, Stranded wire: AWG24 to 14
(Stranded wire is bar terminal can be used in combination.)
Note: UL recognized corresponds, use according to the
following conditions.
・Single wire: AWG22 to 16
・Bar terminal can be not used in combination.
Single wire, Stranded wire: AWG24 to 14
(Stranded wire is bar terminal can be used in combination.)
Note: UL recognized corresponds, use according to the
following conditions.
・Single wire, Stranded wire: AWG24 to 18
・Bar terminal can be not used in combination.
12 to 13mm
Bar terminal
for insert 2 wire
■Example of the optional plug-in module
- 73 -