Over Voltage Alarm Output; Under Voltage Alarm Output; Power Factor Alarm Output - Omron KM1 User Manual

Smart power monitor
Table of Contents

Advertisement

0BChapter 3
Functions

Over voltage alarm output

PMU1A
PMU2A
(Electric
(Power
power)
two-system)
This function is available when output terminal function setting is selected as an alarm
after the setting of alarm parameter setting and alarm output setting.
Alarm judgment implements the OR operation in phases (when the value of a phase
exceeds the over voltage alarm threshold). In addition, release of an alarm implements the
AND operation (when the values of all phases are lower than over voltage alarm threshold
and voltage alarm hysteresis).
Over voltage alarm threshold
Over voltage alarm hysteresis
Over voltage alarm on-delay

Under voltage alarm output

PMU1A
PMU2A
(Electric
(Power
power)
two-system)
This function is available when output terminal function setting is selected as an alarm
after the setting of alarm parameter setting and alarm output setting.
Alarm judgment implements the OR operation in phases (when the value of a phase is
lower than the under voltage alarm threshold). In addition, release of an alarm implements
the AND operation (when the values of all phases exceed under voltage alarm threshold
and voltage alarm hysteresis).
Under voltage alarm threshold
Under voltage alarm hysteresis
Under voltage alarm on-delay

Power factor alarm output

PMU1A
PMU2A
(Electric
(Power
power)
two-system)
This function is available when output terminal function setting is selected as an alarm
after the setting of alarm parameter setting and alarm output setting.
Power factor alarm threshold
Power factor alarm hysteresis
Power factor alarm on-delay
*1. CTD8E (CT expansion) can perform the two-system setting only when it is connected to
PMU2A (power two-system).
3-14
EMU8A
CTD8E
(Pulse/temperature)
(CT
expansion)
×
×
:
:
:
EMU8A
CTD8E
(Pulse/temperature)
(CT
expansion)
×
×
: 0.0 to 12100.0 V (Initial value: 85.0 V)
: 0.0 to 2200.0 V
: 0.1 to 10.0 s
EMU8A
CTD8E
(Pulse/temperature)
(CT
expansion)
×
:-1.00 to 1.00
: 0.00 to 1.00
: 0.5 to 10.0 s
: With two-system alarm
O: With alarm X: Without alarm
0.0 to 12100.0 V
(Initial value: 528.0 V)
0.0 to 2200.0 V
(Initial value: 24.0 V)
0.1 to 10.0 s
(Initial value: 0.1 s)
: With two-system alarm
O: With alarm X: Without alarm
(Initial value: 24.0 V)
(Initial value: 0.1 s)
: With two-system alarm
O: With alarm X: Without alarm
(Initial value: 0.00)
(Initial value: 0.05)
(Initial value: 0.5 s)