0BAppendix
Setting item
Alarm parameter setting for measuring block
1
Alarm parameter setting for measuring block
2
Alarm output setting for measuring block 1
Alarm output setting for measuring block 2
Active power upper limit alarm threshold for
measuring block 1
Active power upper limit alarm hysteresis for
measuring block 1
Active power upper limit alarm on-delay for
measuring block 1
Active power lower limit alarm threshold for
measuring block 1
Active power lower limit alarm hysteresis for
measuring block 1
Active power lower limit alarm on-delay for
measuring block 1
Active power upper limit alarm threshold for
measuring block 2
Active power upper limit alarm hysteresis for
measuring block 2
Active power upper limit alarm on-delay for
measuring block 2
Active power lower limit alarm threshold for
measuring block 2
Active power lower limit alarm hysteresis for
measuring block 2
Active power lower limit alarm on-delay for
measuring block 2
Over current alarm threshold for measuring
block 1
Over current alarm hysteresis for measuring
block 1
Over current alarm on-delay for measuring
block 1
Under current alarm threshold for measuring
block 1
Under current alarm hysteresis for measuring
block 1
Under current alarm on-delay for measuring
block 1
Over current alarm threshold for measuring
block 2
Over current alarm hysteresis for measuring
block 2
Over current alarm on-delay for measuring
block 2
Under current alarm threshold for measuring
block 2
Under current alarm hysteresis for measuring
block 2
Under current alarm on-delay for measuring
block 2
Over voltage alarm threshold for measuring
block 1
Over voltage alarm hysteresis for measuring
block 1
Over voltage alarm on-delay for measuring
block 1
Under voltage alarm threshold for measuring
block 1
Under voltage alarm hysteresis for measuring
block 1
Under voltage alarm on-delay for measuring
block 1
A-12
Initial value
Setting range
0bit: Over voltage alarm
1bit: Under voltage alarm
2bit: Over current alarm
3bit: Under current alarm
4bit: Active power upper limit
alarm
5bit: Active power lower limit
H'00000000
alarm
6bit: Reactive power upper limit
alarm
7bit: Reactive power lower limit
alarm
8bit: Power factor alarm
9bit to 31bit: Idle
0bit: Over voltage alarm
1bit: Under voltage alarm
2bit: Over current alarm
3bit: Under current alarm
4bit: Active power upper limit
alarm
5bit: Active power lower limit
H'00000000
alarm
6bit: Reactive power upper limit
alarm
7bit: Reactive power lower limit
alarm
8bit: Power factor alarm
9bit to 31bit: Idle
1000 W
-120000000~120000000 W
100 W
0~24000000 W
0.5 s
0.5~10.0 s
300 W
-120000000~120000000 W
100 W
0~24000000 W
0.5 s
0.5~10.0 s
1000 W
-120000000~120000000 W
100 W
0~24000000 W
0.5 s
0.5~10.0 s
300 W
-120000000~120000000 W
100 W
0~24000000 W
0.5 s
0.5~10.0 s
100.0 A
0.0~6000.0 A
5.0 A
0.0~1000.0 A
0.1 s
0.1~10.0 s
10.0 A
0.0~6000.0 A
5.0 A
0.0~1000.0 A
0.1 s
0.1~10.0 s
100.0
0.0~6000.0 A
5.0 A
0.0~1000.0 A
0.1 s
0.1~10.0 s
10.0 A
0.0~6000.0 A
5.0 A
0.0~1000.0 A
0.1 s
0.1~10.0 s
528.0 V
0.0~12100.0 V
24.0 V
0~2200.0 V
0.1 s
0.1~10.0 s
85.0 V
0.0~12100.0 V
24.0 V
0.0~2200.0 V
0.1 s
0.1~10.0 s
PMU1A
PMU2A
EMU8A
(Electric
(Power
(Pulse/
power)
two-system)
temperature)
×
×
×
×
×
×
×
×
×
×
×
×
×
×
×
×
×
×
×
×
×
×
×
×
×
×
×
×
×
×
×
×
×
×
×
×
×
×
×
×
×
×
×
×
×
×
×
×
CTD8E
(CT
expansion)
×
×
×
×
×
×