Omron KM1 User Manual page 83

Smart power monitor
Table of Contents

Advertisement

0BChapter 4
Troubleshooting
When
Phenomenon
The primary current of
the inverter cannot be
measured correctly.
The date and time of
the clock are initialized
to April 1, 2012 at
0:0:0.
Communication with
the unit connected
cannot be carried out.
When
used
Data backed up every
5 minutes or alarm
histories for CTD8E
(CT expansion) are
not saved.
Although
communication with
the unit connected can
be carried out, CONN
remains OFF.
4-6
Items to be checked
Action to be taken
Check that the
When the primary current of inverter is measured,
selected dedicated CT
the crest value is several times larger than the
has some margin in
effective value. Therefore, use a dedicated CT
the standard.
having some margin in the standard.
Check whether the
Set the clock all over again.
RTC backup period
has passed.
Check that the
Use the specified connector.
specified connector
has been used.
Check that the settings
Match the setting of the slave ID of the connected
of the connection
unit with that of the connection configuration of the
configuration are
measurement master.
correct.
Check that the power
Power voltage can be applied from the
voltage has been
measurement master to CT expansion slaves only.
applied to the
Apply power voltage to the functional slave.
functional slave.
Check for errors in
Connecting units to each other via the connector,
connections.
match the setting of the slave ID with that of the
connection configuration of the measurement
master.
-
Reset the entire system.
Reference page
A-7
-
2-7
2-3
-
-
-