Reactive power alarm output

PMU1A
PMU2A
(Electric
(Power
power)
two-system)
This function is available when output terminal function setting is selected as an alarm
after the setting of alarm parameter setting and alarm output setting.
Reactive power upper limit alarm threshold : -120000000 to 120000000 var (Initial
Reactive power upper limit alarm hysteresis : 0 to 24000000 var (Initial value: 100 var)
Reactive power upper limit alarm on-delay
Reactive power lower limit alarm threshold : -120000000 to 120000000 var
Reactive power lower limit alarm hysteresis : 0 to 24000000 var (Initial value: 100 var)
Reactive power lower limit alarm on-delay
*1. CTD8E (CT expansion) can perform the two-system setting only when it is connected to
PMU2A (power two-system).

Temperature alarm output

PMU1A
PMU2A
(Electric
(Power
power)
two-system)
×
×
This function is available when output terminal function setting is selected as an alarm
after the setting of alarm parameter setting and alarm output setting.
Upper-limit temperature alarm threshold
Upper-limit temperature alarm hysteresis
Upper-limit temperature alarm on-delay
Lower-limit temperature alarm threshold
Lower-limit temperature alarm hysteresis
Lower-limit temperature alarm on-delay

Reverse phase alarm output

PMU1A
PMU2A
(Electric
(Power
power)
two-system)
This function is available when output terminal function setting is selected as a reverse
phase.
If the condition in which voltage phase order has changed continues for 0.1 s or more, the
alarm output is turned ON.
Setting range: OFF, ON (Initial value: OFF)
* Since the state where phases are not normal is judged as reverse phase, phase-loss may
be judged as reverse phase.
EMU8A
CTD8E
(Pulse/temperature)
(CT
expansion)
×
EMU8A
CTD8E
(Pulse/temperature)
(CT
expansion)
×
EMU8A
CTD8E
(Pulse/temperature)
(CT
expansion)
×
×
: With two-system alarm
O: With alarm X: Without alarm
value: 1000 var)
: 0.5 to 10.0 s (Initial value: 0.5 s)
value: 300 var)
: 0.5 to 10.0 s (Initial value: 0.5 s)
O: With alarm X: Without alarm
: -58.0 to 212.0 (Initial value: 80.0)
: 0.0 to 10.0 (Initial value: 5.0)
: 0.5 to 10.0 s (Initial value: 0.5 s)
: -58.0 to 212.0 (Initial value: 0.0)
: 0.0 to 10.0 (Initial value: 5.0)
: 0.5 to 10.0 s (Initial value: 0.5 s)
: With two-system alarm
O: With alarm X: Without alarm
3.6
Other functions
(Initial
3-15