Advertisement

Control Supply Module (CSM)

9.2 Safety instructions for Control Supply Modules

9.2
Safety instructions for Control Supply Modules
Electric shock when live parts are touched when using the Control Supply Module
The Control Supply Module has 2 supply circuits. Touching live components can result in death
or severe injury.
• Switch off both supply circuits before you start any work.
Electric shock due to the residual charge of the DC-link capacitors
Due to the DC link capacitors, a hazardous voltage is present in the DC link for up to 5 minutes
after the power supply has been switched off.
Contact with live parts can result in death or serious injury.
• Do not open the protective cover of the DC link until 5 minutes have elapsed.
• Verify that the DCP and DCN DC link terminals are de-energized before starting any work.
Electric shock when the protective cover of the DC link is open
Contact with live parts can result in death or serious injury.
• Only operate the components with closed protective cover.
Electric shock due to missing DC-link side covers
Live parts are exposed if the DC link side covers are not fitted. Contact with these live parts could
cause an electric shock.
• Mount the side covers on the first and last component in the drive line-up.
• Order any missing side covers (Article number: 6SL3162-5AA00-0AA0).
Electric shock or fire due to missing or unsuitable overcurrent protective device
Overcurrent protective equipment that trips too late or not all can cause electric shock or fire.
• Connect each Control Supply Module via a suitable circuit breaker or safety fuses.
• The types specified in the technical data for the respective module are to be used in this
• To protect personnel and for fire protection purposes, at the infeed point, the short-circuit
132
WARNING
WARNING
WARNING
WARNING
WARNING
regard. For applications according to IEC, equivalent fuses and circuit breakers are
permissible.
rating and loop impedance must match the specifications in the documentation so that the
installed overcurrent protection devices trip within the specified time.
High Frequency Drive
System Manual, 10/2020, 6SL3097-5AH10-0BP0