Climatic environmental conditions
Long-term storage
Transport
Operation
Mechanical ambient conditions
Long-term storage
Transport
Operation
Vibration test in operation
Shock test in operation
Installation altitude
Operation
Permissible cooling medium temperature (air)
and installation altitude in operation
Product packaging (storage packaging) is individual packaging for storage and does not satisfy the requirements for
1)
transport. Product packaging is therefore not suitable for shipping.
Transport packaging is either packaging that is directly suitable for transport or secondary packaging, which together with
2)
the product packaging satisfies the requirements for transport.
High Frequency Drive
System Manual, 10/2020, 6SL3097-5AH10-0BP0
Class 1K4 according to EN 60721-3-1, in product packaging
Temperature: -25 ... +55 °C
Class 2K4 according to EN 0721-3-2, in transport packaging
Temperature: -40 ... +70 °C
Class 3K3 according to EN 60721-3-3 with increased ruggedness with re‐
spect to relative humidity
Temperature: 0 ... +40 °C without derating
> 40 ... +55 °C with reduction of the output current by 2.67% per °C
Relative humidity: 5 ... 95% no condensation (better than Class 3K3)
Oil mist, salt mist, ice formation, condensation, dripping water, spraying
water, splashing water and water jets are not permitted
Class 1M2 according to EN 60721-3-1, in product packaging
Class 2M3 according to EN 60721-3-2, in transport packaging
Class 3M1 according to EN 60721-3-3
According to IEC 60068-2-6 test Fc (sinusoidal)
10 ... 57 Hz: 0.075 mm deflection amplitude
57 ... 150 Hz: 1 g acceleration amplitude
10 frequency cycles per axis
According to IEC 60068-2-27 test Ea (half-sine)
5 g peak acceleration
30 ms duration
3 shocks in all three axes in both directions
0 ... 1000 m above sea level without derating
> 1000 ... 4000 m
Reduction of the output current by 10% per 1000 meters, or
Reduction in the ambient temperature by 5 °C per 1000 meters
> 2000 ... 4000 m
Operation on line supply systems with grounded neutral point, or
Operation on an isolating transformer with secondary grounded neu‐
tral point
0 °C ... +40 °C and an installation altitude of up to 1000 m without derating,
>40° C to +55 °C: Reduction of the output current by 2.67% per °C
Installation altitude > 1000 ... 4000 m: Reduction in the ambient temper‐
ature by 3.5°C per 500 m.
System overview
3.5 System data
1)
2)
1)
2)
35