Mitsubishi NZ2GFCF-D62PD2 User Manual page 259

Cc-link ie field network high-speed counter module
Table of Contents

Advertisement

(3) Remote registers (RWr10 to RWr17, RWr28 to RWr2F)
Address
(RWr)
Item
CH1 CH2
10
28
Present value
11
29
Latch count value
12
2A
13
2B
Sampling count value
Periodic pulse count,
difference value
14
2C
Periodic pulse count,
15
2D
present value
16
2E
Periodic pulse count
17
2F
value update check
For ΔT
*1
, refer to Page 283, Appendix 4.
2
• This area stores the counter present value.
• The update cycle of this area is ΔT
• When Initial data setting request flag (RY9) is turned off then on, the value in
this area is cleared.
• This area stores the count value latched when the latch counter function
(counter function selection) or the latch counter/preset/replace function is
selected. (For the overview of the operation, refer to Page 133, Section 8.8 or
Page 145, Section 8.12.)
• This area stores the value which is stored in CH Present value (RWr10 to
RWr11, RWr28 to RWr29) of when CH Function input terminal (FUNC1,
FUNC2) or CH Selected counter function start command (RY25, RY3D) is
input.
• When Initial data setting request flag (RY9) is turned off then on, the value in
this area is cleared.
• This area stores the count values in the sampling period when the sampling
counter function is selected. (For the overview of the operation, refer to Page
136, Section 8.9.)
• When Initial data setting request flag (RY9) is turned off then on, the value in
this area is cleared.
• This area stores the count value per cycle time (the difference value) when the
periodic pulse counter function is selected. (For the overview of the operation,
refer to Page 139, Section 8.10.)
• When Initial data setting request flag (RY9) is turned off then on, the value in
this area is cleared.
• This area stores the value which is stored in CH Present value (RWr10 to
RWr11, RWr28 to RWr29) after the cycle time elapsed when the periodic pulse
counter function is selected.
• When Initial data setting request flag (RY9) is turned off then on, the value in
this area is cleared.
• This area stores the same value as the value in CH Periodic pulse count,
difference value (RWr12 to RWr13, RWr2A to RWr2B) when the periodic pulse
counter function is selected.
• When CH Periodic pulse count, difference value (RWr12 to RWr13, RWr2A
to RWr2B) is not equivalent to CH Periodic pulse count value update check
(RWr16 to RWr17, RWr2E to RWr2F), a data mismatch occurs. Read again
CH Periodic pulse count, difference value (RWr12 to RWr13, RWr2A to
RWr2B), CH Periodic pulse count, present value (RWr14 to RWr15, RWr2C
to RWr2D), and CH Periodic pulse count value update check (RWr16 to
RWr17, RWr2E to RWr2F).
• When Initial data setting request flag (RY9) is turned off then on, the value in
this area is cleared.
Description
*1
.
2
APPENDICES
Default
0
A
0
0
0
257

Advertisement

Table of Contents
loading