No.
1)
Counting starts by turning on CH Count enable command (RY24, RY3C).
The value in CH Present value (RWr10 to RWr11, RWr28 to RWr29) is stored in CH Latch count value (RWr12 to RWr13,
RWr2A to RWr2B), and the value in CH Preset value setting (RWw14 to RWw15, RWw2C to RWw2D) is stored in CH Present
2)
value (RWr10 to RWr11, RWr28 to RWr29) at the rising edge of CH Function input terminal (FUNC1, FUNC2). After CH Latch
count value (RWr12 to RWr13, RWr2A to RWr2B) is updated, CH Update flag (Latch count value) (RX29, RX41) turns on.
3)
Set any values to CH Preset value setting (RWw14 to RWw15, RWw2C to RWw2D).
4)
Counting stops by turning off CH Count enable command (RY24, RY3C).
When CH Update flag reset command (Latch count value) (RY28, RY40) is turned off then on, the high-speed counter module
turns off CH Update flag (Latch count value) (RX29, RX41) and turns on CH Update flag reset completed (Latch count value)
5)
(RX28, RX40).
After that, CH Update flag reset completed (Latch count value) (RX28, RX40) turns off when CH Update flag reset command
(Latch count value) (RY28, RY40) is turned off.
6)
Counting resumes by turning on CH Count enable command (RY24, RY3C).
● The count value cannot be replaced with the preset value while CH External preset/replace (Z Phase) request
detection (RX23, RX3B) is on.
Replace the value after CH External preset/replace (Z Phase) request detection (RX23, RX3B) turns off by turning on
CH External preset/replace (Z Phase) request detection reset command (RY23, RY3B).
● Have a ΔT
or longer interval after changing CH Preset value setting (RWw14 to RWw15, RWw2C to RWw2D) until the
1
value is replaced since there are maximum of ΔT
● When the latch counter function is performed by CH Function input terminal (FUNC1, FUNC2), the operation response
time follows CH Function input response time setting (address: 0129
count value (RWr12 to RWr13, RWr2A to RWr2B) is updated synchronizing with the internal control cycle, a maximum of
delay time shown below occurs until the acquired value is stored.
*1
• ΔT
+ Setting time of CH Function input response time setting (address: 0129
1
For ΔT
*1
, refer to Page 283, Appendix 4.
1
Description
delay until change in the preset value is reflected.
1
.b2 to b3, 0149
H
CHAPTER 8 FUNCTIONS
*1
.b2 to b3). Since CH Latch
H
.b2 to b3, 0149
.b2 to b3)
H
H
147