Nec Power-Limited Wiring Requirements For Maximal11 - Altronix Maximal Series Installation Manual

Access power controllers
Hide thumbs Also See for Maximal Series:
Table of Contents

Advertisement

NEC Power-Limited Wiring Requirements for Maximal11:

Power-limited and non power-limited circuit wiring must remain separated in the cabinet. All power-limited circuit wiring
must remain at least 0.25" away from any non power-limited circuit wiring. Furthermore, all power-limited circuit wiring
and non power-limited circuit wiring must enter and exit the cabinet through different conduits. One such example of this
is shown below. Your specific application may require different conduit knockouts to be used. Any conduit knockouts may
be used. For power-limited applications use of conduit is optional. All field wiring connections must be made employing
suitable gauge CM or FPL jacketed wire (or equivalent substitute).
Note: Refer to wire handling drawing below for the proper way to install the CM or FPL jacketed wire (Fig. 6a).
Fig. 6
Optional Battery
Enclosure
(non power-limited)
Fig. 6a
Incorrect Wire
Handling
Wire
Insulation
Solid Copper
Conductors
Maximal11/Maximal33/Maximal55/Maximal77/Maximal75 Access Power Controllers (Fused)
External UL Listed Power-Limited,
Access Control Power Supply
12 to 24VAC or DC
115VAC Input
60Hz
(non power-limited)
Correct Wire
Handling
External
Jacketed
Shield
Pull back
external jacketed
shield approx. 1/2".
Available from A1 Security Cameras
www.a1securitycameras.com email: sales@a1securitycameras.com
Supervisory
Connections
(power-limited)
Battery Connections
(non power-limited)
ACM8
outputs
(power­
limited)
- 13 -