Maximal Installation Instructions - Altronix Maximal Series Installation Manual

Access power controllers
Hide thumbs Also See for Maximal Series:
Table of Contents

Advertisement

• Fire Alarm disconnect (latching or non-latching) is individually selectable for any or all of the sixteen (16) outputs.
Fire Alarm disconnect input trigger options:
a) Normally open (NO) or normally closed (NC) dry trigger input.
b) Polarity reversal input from FACP signaling circuit.
• Green LED on ACM8 board indicates FACP disconnect is triggered.
• FACP output relay indicates that FACP input is triggered (form "C" contact rated @ 1A/28VDC not evaluated by UL).
• Power supply input options:
a) Factory installed power supplies provide common power for both ACM8 boards and all connected
access control devices.
b) An optional UL Listed power-limited external access control power supply may be connected to isolate
the ACM8 boards from the access control devices (only applicable on Maximal11).
• ACM8 board main fuses are rated @ 10A. Output fuses are rated @ 3.5A.
• Built-in charger for sealed lead acid or gel type batteries.
- Maximum charge current is 0.7A for AL400ULXB2, AL600ULXB and AL1012ULXB power supply boards.
- Maximum charge current is 3.6A for AL1024ULXB2 power supply board.
• Automatic switch over to stand-by battery when AC fails.
• Zero voltage drop when unit switches over to battery backup (AC failure condition).
• Short circuit and thermal overload protection with auto reset.
• Green AC input and red DC output LED indicators on power supply board(s).
• AC fail supervision (form "C" contact rated @ 1A/28VDC).
• Battery fail and battery presence supervision (form "C" contact rated @ 1A/28VDC).
• Enclosure accommodates up to four (4) 12VDC/12AH batteries.
Enclosure dimensions: 26" x 19" x 6.25" (660.4mm x 482.6mm x 158.8mm).
Wiring methods shall be in accordance with the National Electrical Code/NFPA 70/ANSI, and with all local codes and
authorities having jurisdiction. Product is intended for indoor use only.
Power Supply Board LED Diagnostics
Access Power Controller LED Diagnostics
Power Supply Board Terminal Identification
Access Power Controller Terminal Identification
Power Supply Board Stand-by Battery Specifications
Power Supply Board Output Voltage Settings
Access Power Controller Typical Application Diagram
FACP/Optional Power Supply Hook-up Diagrams
1. Mount unit in the desired location. Mark and predrill holes in the wall to line up with the top three keyholes in the
enclosure. Install three upper fasteners and screws in the wall with the screw heads protruding. Place the enclosure's
upper keyholes over the three upper screws, level and secure. Mark the position of the lower three holes.
Remove the enclosure. Drill the lower holes and install the three fasteners. Place the enclosure's upper keyholes
over the three upper screws. Install the three lower screws and make sure to tighten all screws
Enclosure Dimensions, pg. 18).
2. The power supply is pre-wired to the ground (chassis). Connect main incoming ground to the provided green
grounding conductor lead. Connect unswitched AC power (115VAC 60Hz) to the terminals marked [L, N] on both
power supply boards. Use 14 AWG or larger for all power connections.
Keep power-limited wiring separate from non power-limited wiring (120VAC 60Hz Input, Battery Wires).
Minimum 0.25" spacing must be provided.
CAUTION: Do not touch exposed metal parts. Shut branch circuit power before installing or servicing equipment.
There are no user serviceable parts inside. Refer installation and servicing to qualified service personnel.
3. Select desired DC output voltage by setting SW1 to the appropriate position on the power supply board (Maximal11
and Maximal33), (Fig. 1, pg. 9). Maximal55 power supply is factory set at 12VDC. Maximal77 power supply is
factory set at 24VDC. Maximal75 consists of one (1) power supply board that is factory set at 12VDC, and one (1)
power supply board that is factory set at 24VDC.
4. Measure the output voltage of the unit before connecting any devices to ensure proper operation.
Improper or high voltage will damage these devices.
- 4 -

Maximal Installation Instructions:

Available from A1 Security Cameras
www.a1securitycameras.com email: sales@a1securitycameras.com
(pg. 6)
(pg. 6)
(pg. 6)
(pg. 7)
(pg. 7)
(pg. 8)
(pg. 8)
(pg. 16)
Maximal11/Maximal33/Maximal55/Maximal77/Maximal75 Access Power Controllers (Fused)

Advertisement

Table of Contents
loading

This manual is also suitable for:

Maximal11Maximal55Maximal77Maximal75Maximal33

Table of Contents