Remove The Com Connecting Cable On The 3Rw50 Soft Starter - Siemens SIRIUS 3RW5 Equipment Manual

Ethernet/ip communication module
Hide thumbs Also See for SIRIUS 3RW5:
Table of Contents

Advertisement

Connection
5.1 COM connecting cable
5.1.4

Remove the COM connecting cable on the 3RW50 soft starter

Requirements
● 3RW50 soft starter
● Removed hinged cover
Further information on removing the hinged cover can be found in the Equipment Manual
of the 3RW50 soft starter.
● COM connecting cable removed from the 3RW5 communication module (Page 53)
Procedure
Illustration similar
1. Loosen die securing mechanism on the bus connector of the COM connecting cable.
2. Pull the bus connector of the COM connecting cable out of the socket on the
3RW50 soft starter.
3. Install the hinged cover.
Further information on installing the hinged cover can be found in the Equipment Manual
of the 3RW50 soft starter.
Result
You have disconnected the COM connecting cable from the 3RW50 soft starter.
54
SIRIUS 3RW5 EtherNet/IP communication module
Equipment Manual, 03/2020, A5E45131885002A/RS-AB/002