Procedure
...
1. Integrate the 3RW5 Soft Starter in the configuration software of the controller with the
EDS file as an adapter in the EtherNet/IP system (Page 69).
2. The following procedures are possible:
– Configuration with DHCP: Set the IP parameters with DHCP using a BOOTP/DHCP
– Configuration without DHCP: Address the adapter (3RW5 Soft Starter) in the
Note the information in chapter IP parameters (Page 66).
3. The following procedures are possible:
– Configuration with DHCP: Transfer the IP parameters to the
– Configuration without DHCP: Set the required IP parameters via the TCP/IP Interface
Note the information in chapter IP parameters (Page 66).
4. Enter the changed IP parameters of the adapter in the configuration software of the
controller.
Note the information in chapter IP parameters (Page 66).
5. Load the configuration into the scanner (if required).
SIRIUS 3RW5 EtherNet/IP communication module
Equipment Manual, 03/2020, A5E45131885002A/RS-AB/002
Programmable logic controller / scanner
PC or programming device with configuration software of controller
EtherNet/IP
SIRIUS 3RW5 Soft Starter / adapter
: Steps to be taken in the procedure
server tool.
configuration software of the controller using the IP parameters currently stored in the
3RW5 EtherNet/IP communication module.
3RW5 communication module using the MAC address. Ignore Step 4 of the
procedure.
Object (Page 135) in the 3RW5 soft starter.
6.2 Configuring the 3RW5 soft starter
Configuring
63