CS-VG120KE / CU-VG120KE
8.10. QUIET OPERATION
The purpose of this control is to reduce indoor operating noise. Indoor fan speed is set to Lo- when the following conditions occur.
∙ Indoor fan speed is set at Low
∙ Indoor heat exchanger temperature rises to 17°C or above
∙ Compressor operates for 5 minutes or above
∙ Operation frequency is less than 45Hz
When the indoor heat exchanger temperature is decreased to 13C or below, the control is cancelled and the indoor fan speed
will resume from Lo- to Low.
8.11. POWERFUL MODE OPERATION
When the powerful mode is selected, the internal setting temperature will shift to achieve the setting temperature quickly.
1. Cooling Operation
2. Soft Dry Operation
3. Heating Operation
28